AC/DC current transformer with energy meter functionality 

SIRAX 

BT7300 / BT7350

 

    

              

Safety instructions

The unobjectionable and hazard-free operation presupposes that the 
safety instructions as well as Device Manual, electronically downloa-
dable via www.camillebauer.com, have been read and understood.

Please refer to our operating instructions for details. Downloadable 
from our website www.camillebauer.com

The installation and commissioning should only be carried out by trained 
personnel.
Check the following points before commissioning:
- that the connection wires are not damaged, and that they are not live during 

wiring

- that the power flow direction and the phase rotation are correct
The instrument must be taken out of service if safe operation is no longer pos-
sible (e.g. visible damage). In this case, all the connections must be switched 
off. The instrument must be returned to the factory or to an authorized service 
dealer.
It is forbidden to open the housing and to make modifications to the instrument. 
The instrument is not equipped with an integrated circuit breaker. During instal-
lation check that a labeled switch is installed and that it can easily be reached 
by the operators.
The device is maintenance free. Unauthorized repair or alteration of the unit 
invalidates the warranty.

Application area

The SIRAX BT7300 and BT7350 are current transformer with energy meter functionality 
for monitoring 1-phase AC and DC systems up to a maximum current of 300 A AC and 
400 V DC, and up to a maximum voltage of 800 V AC and 1000 V DC. The current 
measurement is galvanically separated from the measured line. With the ability to 
measure currents with different frequency ranges, the AC/DC current transformers are 
the ideal solution for monitoring photovoltaic systems, battery charging systems, UPS 
systems, variable frequency drives.

      

Mounting and installation

Ensure a safe working environment during assembly, installation 
and maintenance work. Disconnect the power supply of the 
primary conductor and secure it against unintentional reconnec-
tion.

•  Mounting is via screw grooves for vertical and horizontal panel mounting or 

via fastening elements for vertical and horizontal DIN rail mounting.

•  The installation of the devices is arbitrary.
•  Now connect the device according to the wiring diagram.

Electrical connections

Attention: Danger to life! Ensure that all leads are free of potential 
when connecting them!

Please observe that the data on the type plate must be adhered to !
The national provisions have to be observed in the installation and 
material selection of electric lines!

Technical data

SIRAX BT7300

SIRAX BT7350

Input

Type of measure

TRMS (monopolar) or DC

Available measurands

I

rms

; V

rms

; Watt, VAR; VA; V

pk

; I

pk

; Freq; Cosφ; THD; ΣkW; +kW/h; -kW/h; 

min/max of rms measurement

Input range current

300 A AC / 400 A DC

Input range voltage

800 V AC / 1000 V DC

80 V AC / 100 V DC

Power supply

9 ... 30 V DC

Absorption

< 1.3 W

Output

Output range

RS485 (Modbus RTU)

Sampling rate

11k Samples per Second

Working frequency

DC or 1 ... 400 Hz

Accuracy

Accuracy
(@25°C up to 400Hz)

Voltage, Current, Active Power: < 0.5% F.S.

Frequency: ± 0.1 Hz

Energy: ± 1% of reading

V

peak

, I

peak

: ± 5% F.S.

Resolution

12 bit

Temperature coefficient

< 200 ppm/°C

Crest factor

1.4 (on current measurement)

Input impedence

1 MΩ ±1%

Environmental conditions

Working temperature

-15 ... +65 °C

Storage temperature

-40 ... +85 °C

Humidity

10 ... 90 % (not condensing)

Altitude

max 2000 m

Safety

Overvoltage category

CATIII up to 600 V; CATII up to 1000 V

CATIV up to 100 V

Isolation

3 kV on bare wire for Current measurement;

4 kV for Voltage measurement

Protection class

IP20

Mechanical properties

Housing material

PTB

Filling

Epoxy Resins

Flammability

UL94 V-0, self-extinguishing, non-dripping, halogen-free

Weight

370 g

DIP switch

2 pole

LED

Permanent yellow (Power ON)

Blinking yellow (communication)

Permanent yellow (Power ON)

Dimensions

89.1 x 99.25 x 28.5 mm (without terminals)

Connections

Connections

Plug-in terminals 3.5 mm, 1x4 Pole and 2x2 Pole 

Cross-sectional area

1.5 mm

2

Torque

max 0.25 Nm

Standards

Adhered standards

EN61000-6-4; EN64000-6-2; EN61010-1

DIP switch settings BT7300 / BT7350

Description

1

2

All settings from EEPROM

0

0

Set Address 1 - Baud 9600

1

0

Set Address 1 - Baud 38400

1

1

Configuration via software

The SIRAX BT7300 and BT7350 can be configured via the free programming software. 
This is downloadable on our homepage. The programming instructions can be found in 
the corresponding operating manuals for the products.

Connection scheme BT7300 / BT7350

V

Vg

RS485

USB

LOAD

± 1000 / 100 VDC

± 800 / 80 VAC

Содержание SIRAX BT7300

Страница 1: ...nt AC DC avec fonctionnalit de compteur d nergie SIRAX BT7300 BT7350 4 Indicazioni per la sicurezza Trasformatore di corrente AC DC con funzionalit di contatore di energia SIRAX BT7300 BT7350 5 Instru...

Страница 2: ...e der Ger te ist beliebig Schliessen Sie nun das Ger t gem ss Anschlussschema an Elektrische Anschl sse Achtung Lebensgefahr Sicherstellen dass beim Anschluss alle Leitungen spannungsfrei sind Es ist...

Страница 3: ...cal and horizontal DIN rail mounting The installation of the devices is arbitrary Now connect the device according to the wiring diagram Electrical connections Attention Danger to life Ensure that all...

Страница 4: ...l ments de fixation pour montage sur rail DIN vertical et horizontal La position d utilisation est quelconque Maintenant connectez l appareil conform ment au sch ma de c blage Connexions lectriques At...

Страница 5: ...montaggio dei dispositivi arbitraria Ora collegare il dispositivo secondo lo schema elettrico Connessioni elettriche Attenzione Pericolo di morte Assicurarsi che l apparechcio non sia in tensione quan...

Страница 6: ...ical y horizontal La posici n de montaje de los dispositivos es arbitraria Ahora conecta el dispositivo de acuerdo con el diagrama de cableado Conexi n el ctrica Peligro de muerte Aseg rese de que los...

Страница 7: ...r Bitte beachten Explication de signe Les appareils ne doivent tre limin s que de fa on appropri e Sigle de conformit CE Attention Point dangereux g n ral Tenir compte du mode d emp loi Attention Dang...

Страница 8: ...0 Aac 80 Vac 100 Vdc TRMS AC DC 1 ph energy meter Cat IV 100V 99 25 33 00 89 10 71 05 Dimensionen Dimensions Dimensionis Dimensioni Dimensiones SIRAX BT7300 400 Adc 300 Aac 800 Vac 1000 Vdc TRMS AC DC...

Отзывы: