Door Module Installation
The door frame presents itself with a stiff 30mm
flange including a 10mm backbend.
This can be used for fully flush or on-top wall
integration.
Insert the frame into the wall cutout and fix with
bolts (2 top & 2 bottom) to the unit.
Fixing holes in the wall flange are elongated to
allow for compensation of slight alignment errors.
After installation and adjustment, fill the conical gap
between door frame and wall-flange with sealant to
obtain an airtight fit.
Door panels close by gravity
(push top to open).
As an option they can be fitted
with push-push mini-latches for
mechanical lock.
At an opening angle of approx.
30°, the panel(s) can be simply
lifted out for unobstructed
access to the filter stack.
apply