10
Section 2
Model 580A Differential Pressure Switch
IMPORTANT: Arc suppression for inductive loads will prolong the life of the switch
contacts.
Startup
For startup procedures, warnings, and other information on the Model 224
DPU, see
Appendix A, page A-1
.
IMPORTANT: To ensure the unit calibration is within factory-set calibration tolerances,
perform the Calibration Check procedure on
page 12
.
Switch Wiring
IMPORTANT: Figure 2.1 shows switch contacts in the relaxed (shelf) condition, the low
switch set to trip at a position below the pointer scale position, and the
high switch set to trip at a position above the pointer scale position. NO
= Normally Open in (shelf) condition. NC = Normally Closed in (shelf)
condition. C= Common.
LOW & HIGH SPDT SWITCHES
NO
NO
C
C
NC
NC
RED
YELLOW
BLUE
RED
YELLOW
BLUE
WHITE
GREEN
BLACK
WHITE
GREEN
BLACK
1 2 3 4 5 6 7 8
9 10
Figure 2.1—Low/high SPDT switch diagrams
Table 2.1—Switch Wire Color Coding
580A Current Configurations
NO
C
NC
Low
Red
Yellow
Blue
High
Black
Green
White
Содержание BARTON 580A
Страница 8: ...8 Section 1 Model 580A Differential Pressure Switch ...
Страница 28: ...28 Section 4 Model 580A Differential Pressure Switch Figure 4 2 Model 580A 2 blind switch without indicator ...
Страница 32: ...32 Section 4 Model 580A Differential Pressure Switch ...
Страница 54: ...A 20 Appendix A Model 580A Differential Pressure Switch ...
Страница 56: ......