P
age
27
- Manual
FA01554-EN
- 01/2021 - © C
AME S.p.A. - The contents of this manual may be changed at any time and without notice. - T
ranslation of the o
riginal instructions
Safety devices test
Check that the photocells connected to the selected inputs are operating correctly, after each opening and closing command.
To run the check, the photocells must be connected using the TS terminal as indicated in the “Safety devices”
section.
F5
Safety devices test
OFF (Default)
1 = CX
2 = CY
3 = CX+CY
Hold-to-run
With the function active, the operator stops moving (opening or closing) when the control device is released.
When the function is active, it excludes all other control devices.
F6
Hold-to-run
OFF (Default)
ON
Command 2-7
Associate a command with the device connected to 2-7.
F7
Command 2-7
0 = Step-by-step (default)
1 = Sequential
Gate-open warning light
It signals the gate status. Device connected to output/terminal 5.
F10
Gate-open warning light
0 = Warning light on (default) - The warning light stays on
when the gate is moving or open.
1 = Warning light fl ashing - The warning light fl ashes
every half second when the gate is opening and stays on
when the gate is open. The light fl ashes every second
when the gate is closing, and remains off when the gate
is closed.
Encoder
Use the encoder input from the motor.
F11
Encoder
ON (Default)
OFF
Closing thrust
When the leaves reach the closing limit-switch, the operator thrusts them towards the strike plate for a second.
F13
Closing thrust
OFF (Default)
1 = Minimum thrust
2 = Medium thrust
3 = Maximum thrust