Courtesy time
F25
Set the lighting device operation time.
60 to 180 seconds (Default 180 seconds)
Opening and closing speed
F28
Set the opening and closing speed.
For booms complete with accessories (swing rest and/or skirt), reduce the
speed.
MIN = minimum speed
MED = average speed
MAX = maximum speed
XMA = maximum speed for boom <3m
Slowdown speed
F30
Set the slowdown speed.
MIN = minimum speed
MED = average speed
MAX = maximum speed
Calibration speed
F33
Set the travel self-learning speed (percentage of maximum speed).
20% to 40%
Travel sensitivity
F34
It adjusts the obstacle detection sensitivity during the gate travel.
10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity
Slowdown sensitivity
F35
Adjust the obstruction detection sensitivity during slowdown in percentage terms.
10% to 100% (Default 100%)
10% = minimum thrust and high obstruction sensitivity
100 % =maximum thrust and low obstruction sensitivity