7 Selecting functions
10-WAY DIP-SWITCH
SPEED/SENS TRIMMER =
Adjustments
adjusting amperometric sensitivity while gate is moving: min/max.
DECEL/SENS =
Adjustments
amperometric sensitivity during deceleration: min/max.
Trimmer T.C.A. =
Adjustments
automatic closing time from a minimum of 1 seconds to a maximum of 120 seconds”
.
1 ON -
Automatic closing activated ;
2 ON
-
Operating the activated “
open/close/invert
”
" button or radio command
;
2 OFF
-
Operating the activated “
open/stop/close/stop
”
" button or radio command
;
3 ON
-
Operating the activated "open only" ”
radio command
;
4 ON
-
Prefl ashing
duringt opening and closing activated ;
5 ON
-
Obstacle detection
activated
;
6 ON
-
Maintained action activated operation
” ; (excludes the radio command function)
7 ON
-
Ramming function activated ; (for easier lock releasing)
8 OFF
-
Partial stop activated with safety device connected to terminals 2-C3, (if unused, set DIP switch to ON)
;
9 OFF
-
"Stop" button activated
; with safety device connected to terminals 1-C2, (if unused, set DIP switch to ON)
10 -
2 - Must stay OFF
8.1 Trimmers
8 Settings
8.2 Adjusting the operating time
To memorise the operator's working time (from when it starts to open to when it is fully closed) you need to:
1. set Dip-switch 6 to ON;
2. press CH1 until gate is fully opened;
3. press CH2 and release it when the gate is completely closed;
4. Set dip-switch 6 back to OFF.