F19
Automatic
Closing Time
The automatic-closing wait starts when the opening limit switch point is reached
and can be set to between 1 and 180 seconds. The automatic closing does not
work if any of the safety devices trigger when an obstruction is detected, or
after a total stop, or during a power outage.
OFF
= Deactivated (
default
) /
1
= 1 second /... /
180
= 180 seconds
F20
Automatic
closing time
after partial
opening
The automatic-closing wait starts when the partial opening point is reached (from
partial opening command) and can be set to between 1 and 180 seconds. The
automatic closing does not activate, after a total stop or if the power supply is
missing.
The F19 function must not be deactivated.
OFF
= Deactivated
(default)
/
1
= 1 second /... /
180
= 180 seconds
F21
Pre-fl ashing time
Adjusting the pre-fl ashing time for the fl ashing light connected to 10-E before each
maneuver. The fl ashing time is adjustable from 1 to 10 seconds.
OFF
= Deactivated
(default)
/
1
= 1 second /... /
10
= 10 seconds
F25
Courtesy light
time
The courtesy light stays lit for the necessary time while the door is opening and
closing.
Adjustable between 60 and 180 seconds.
60
= 60 seconds /... /
180
= 180 seconds
(default)
F34
Travel
sensitivity
It adjusts the obstacle detection sensitivity during the gate travel.
Change the parameter in compliance with the regulations on impact
force.
50
= Maximum sensitivity (default) /… /
100
= Minimum sensitivity
F36
Adjusting the
partial opening
Adjustment as a percentage of total travel, during the door partial opening.
5
= 5% of the travel /… /
40
= 40% of the travel
(default)
/… /
80
= 80% of the
travel.
F58
Maintenance
maneuvers
With this function it is established how many maneuvers the motor must perform to
display the maintenance request.
F60
Sleep mode
he function switches off the 10-2 power when the motor is stationary.
OFF
= deactivated (default) /
ON =
activated
F80
Sound signal
OFF
= (default) deactivated /
ON
= activated
If activated, the buzzer will emit a signal each time any programming key is pressed
and, with the automatic closing time activated, it emits an acoustic signal warning
that the door is closing.
p.
26
-
Ma
nu
al
FA01742-EN
- 12/2021 - © CAME S.p.A. -
Th
e c
onte
nts of th
is
m
an
ua
l m
ay b
e c
ha
ng
ed, at a
ny ti
m
e, a
nd w
ith
ou
t n
oti
ce
. - O
rig
in
al
in
str
ucti
on
s
Содержание VER06DES
Страница 1: ...VER06DES VER08DES IT Italiano EN English FR Français RU Pусский FA01742M04 ...
Страница 2: ......
Страница 33: ...Garage door operator Series VER VER06DES VER08DES INSTALLATION MANUAL EN English FA01742 EN ...
Страница 34: ......
Страница 65: ...Automatisme pour portes de garage Série VER VER06DES VER08DES MANUEL D INSTALLATION FR Français FA01742 FR ...
Страница 66: ......
Страница 98: ......