Closing speed
Set the closing speed (percentage of maximum speed).
The percentage values automatically adapt to the value entered in the function [Boom length].
F29
Closing speed
from 60% to 100% (Default 50%)
Travel sensitivity
Adjust the obstruction detection sensitivity during boom travel.
F34
Travel sensitivity
10% to 100% (Default 100%) - 10% = maximum sensitivity - 100% = minimum
sensitivity
RSE1
Configure the function to be performed by the card inserted in the RSE1 connector.
F49
RSE1
OFF (Default)
1 = Paired
4 = Alternate
Save data
Save user data, timings and configurations to the memory device (memory roll or USB key).
The function is displayed only when a USB stick is inserted into the USB port or when a memory roll card is inserted into the control board.
F50
Save data
OFF (Default)
ON
Read data
Upload user data, timings and configurations from the memory device (memory roll or USB key).
The function is displayed only when a USB stick is inserted into the USB port or when a memory roll card is inserted into the control board.
F51
Read data
OFF (Default)
ON
Transferring MASTER-SLAVE parameters
Enable the sharing of parameters programmed on the Master barrier with the Slave barrier.
This only appears if the F49 function is set to Paired or Alternate.
F52
Transferring MASTER-SLAVE
parameters
OFF (Default)
ON
Opening direction
Set the boom opening direction.
F54
Opening direction
0 = To the left (default)
1 = To the right
CRP address
Assign a unique identification code (CRP address) to the control board. It is used where there are multiple operators connected via CRP.
F56
CRP address
from 1 to 255