Dip 10-way
SELECTION FUNCTIONS
1
ON
Parameter storage (used during calibration pag. 17).
2
ON
Checking the charge level on the emergency (whit MA7032. see pag.18).
3
-
Not used. keep the dip in position "OFF".
4
ON
Constant push while closing
5
ON
"Step-by-step" operation (see contact 2-M. pag.14).
6
ON
Interface with other automation system (see "installing the interface system" pag.20).
7/8
ON
Disabled electric Iod< (see pag.19).
7
ON
Continuous operation of Iod< (Iod<s doors open and closed) see pag.19
8
OFF
7
OFF
Continuous operation of lock (locks doors closed) see pag.19
8
ON
7/8
OFF
Electric lock disengaged from local control (controlled by function switch MA7041) pag.19
9/10
ON
Emergency system closes doors in case of power failure (see pag.18)
9
OFF
Emergency system opens doors in case of power failure (see pag.18)
10
ON
9/10
OFF
Normal operation powered by emergency battery in case of power failure (see pag.18)
Dip 4-way
SELECTION FUNCTIONS
1
ON
Activation of spring-loaded anti-panic device (set dip switch 4 to ON. constant push while closing.
1D-dip function selector. see pag.19).
2
-
Not used. keep the dip in position "OFF"
3
ON
Excludes the photoelectric cell function (MF9011 or MF9111 card Inserted into the control board.
pag.22)
4
-
Not used. keep the dip in position "OFF"
,
•
FUNCTIONS
OF INDICATOR
LED
~
CD CD CD CD CD CD CD CD
, BilE
1 2 3 4 5 6 7 8
._--
_.
LED
STATUS
SIGNAL
1
flashing
-Encoder is inoperative
1
lit
-Encoder is inoperative
2
('J
-emergency battery is discharged
3
lit
-pilot light on 24V a.c.
4
lit
-photocell contact open
5
lit
-interlace function activated (see "installing the interlace-)
6
lit
-malfunction on electrick lock
7
lit
-pilot light on amperometric sensor
8
flashing
-automatic closing cycle in progress
8
nashing
-"read" error during automatic calibration cycle
6/7/8
lits
-automatic calibration procedure terminated
('J
in this case. the LED signal remains lit to indicate that the anti-panic device balleries are run down only if the
emergency battery status check is disabled (1O-waydip 2 set to OFF); whereas it flashes
if
the battery check is activated
(10-way dip 2 set to ON).
,.