Determining the closing end-of-travel points

 Perform the operations on both gearmotors.

Release the gearmotor.
Manually close the leaf to the desired point.
Disconnect the 9-pole terminal board.
Connect the multimeter set to check continuity to the Rc-Rc terminals (NC contact); a buzzer will sound on the multimeter.
Turn the shaft (C) ANTICLOCKWISE to determine the closing travel end point, until the Rc-Rc contact opens and the multimeter stops buzzing.

 If you want to decrease the closing angle, the multimeter will buzz again: turn the shaft CLOCKWISE until the multimeter stops buzzing.

 If you want to increase the closing angle, the multimeter will buzz again: turn the shaft ANTICLOCKWISE until the multimeter stops buzzing.

 Leave the rod nut loose to determine the end-of-travel points.

M  N

Rc Rc

Ra Ra +   E   -

Ω

V

Hz

After adjusting the travel end points, run travel self-learning from the control panel, following the instructions in the control panel manual.

Содержание ATS50DGS

Страница 1: ...Gearmotor for swing gates ATS30DGS ATS50DGS ATS30DGR INSTALLATION MANUAL FA01561 EN EN English...

Страница 2: ...1 2 3 1 2 3 4...

Страница 3: ...tc Make sure you have set up a suitable dual pole cut off device along the power supply that is compliant with the installation rules It should completely cut off the power supply according to categor...

Страница 4: ...tegies Simply follow these brief disposal guidelines DISPOSING OF THE PACKAGING The packaging materials cardboard plastic etc can be disposed of easily as solid urban waste separated for recycling Bef...

Страница 5: ...rsible telescopic gearmotor 24 V with encoder for swing gates with Max C up to 200 mm with leaf up to 5 m and 400 kg Grey RAL7024 801MP 0110 ATS30DGR Irreversible telescopic gearmotor 24 V with encode...

Страница 6: ...pressure level dB A 70 70 70 Protection rating IP 54 54 54 Insulation class I I I Reduction ratio i 28 28 28 Weight kg 7 5 8 7 5 Cable types and minimum thicknesses Cable length m up to 20 from 20 to...

Страница 7: ...for fitting the operator and accessories varies depending on the area where it is installed It is up to the installer to find the most suitable solution The drawings refer to a gearmotor installed on...

Страница 8: ...leaf to 90 or 120 First determine where the gate bracket needs to be positioned then where the post bracket needs to be positioned Respect the values indicated in the table A C B 60 60 E F 5 ATS30DGS...

Страница 9: ...ithout notice Translation of the original instructions Fastening the brackets Secure the post bracket with plugs and screws The holes on the bracket fixing plate allow you to vary the opening angle of...

Страница 10: ...hanged at any time and without notice Translation of the original instructions Fastening the gearmotor Lubricate all moving parts on the operator A The self locking nut must be loosely tightened so as...

Страница 11: ...ICAL CONNECTIONS Before working on the control panel disconnect the mains power supply and remove the batteries if any Remove the protective cover to access the terminal board A Control panel B Gearmo...

Страница 12: ...form the operations on both gearmotors Release the gearmotor Manually open the leaf to the desired point Disconnect the 9 pole terminal board Connect the multimeter set to check continuity to the Ra R...

Страница 13: ...on the multimeter Turn the shaft C ANTICLOCKWISE to determine the closing travel end point until the Rc Rc contact opens and the multimeter stops buzzing If you want to decrease the closing angle the...

Страница 14: ...tablishing the bracket fastening points Close the gate manually First determine where the gate bracket needs to be positioned then where the post bracket needs to be positioned Respect the values indi...

Страница 15: ...ical connections Before working on the control panel disconnect the mains power supply and remove the batteries if any Remove the protective cover to access the terminal board A Control panel B Gearmo...

Страница 16: ...el range To move the microswitch 10 mm in either direction turn the rod 20 times A C Determining the opening end of travel points Perform the operations on both gearmotors Release the gearmotor Manual...

Страница 17: ...the 9 pole terminal board Connect the multimeter set to check continuity to the Ra Ra terminals NC contact a buzzer will sound on the multimeter Turn the shaft A CLOCKWISE to determine the closing tr...

Страница 18: ...If the system is not used for long periods of time e g for installations at sites with seasonal closures disconnect the power supply When the power supply is reconnected check the system is working c...

Страница 19: ...Page 19 Manual FA01561 EN 02 2021 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 20: ...AME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions CAME S p A Via Martiri della Libert 15 31030 Dosson di Casier Treviso Italy...

Страница 21: ...ZL65 INSTALLATION MANUAL FA01359 EN EN English...

Страница 22: ...led and quali ed personnel and in full compliance with the regulations in force The device must be installed wired connected and tested according to good professional practice in compliance with the s...

Страница 23: ...ntrol this must be installed at a minimum height of 1 5 m from the ground and must not be accessible to the public If not already present apply a permanent tag that describes how to use the manual rel...

Страница 24: ...ging materials cardboard plastic etc can be disposed of easily as solid urban waste separated for recycling Before dismantling and disposing of the product please always check the local laws in force...

Страница 25: ...ed are in millimetres Description 002ZL65 Control panel for one or two leaf swing gates with programming display on board radio decoding and self diagnosing safety devices Technical data MODELS ZL65 P...

Страница 26: ...es 8 Terminal board for CRP connection 9 Terminal board for connecting the transponder selector switch 10 Terminal board for connecting the keypad selector 11 Terminal board for connecting the antenna...

Страница 27: ...V and outdoors use H05RN F cables compliant with 60245 IEC 57 IEC when operating indoors use H05VV F cables compliant with 60227 IEC 53 IEC For power supplies up to 48 V you can use FROR 20 22 II cab...

Страница 28: ...nts of this manual may be changed at any time and without notice Translation of the original instructions INSTALLATION Preparing the control panel 1 Separate the parts of the control panel 2 Drill the...

Страница 29: ...anslation of the original instructions Fastening the control panel 1 Drill the xing points in the control panel in a protected area 2 Fasten the base using screws and plugs Use Phillips round head scr...

Страница 30: ...hout notice Translation of the original instructions ELECTRICAL CONNECTIONS Preparing the electrical cables Connect all wires and cables in compliance with the law Use cable glands to connect the devi...

Страница 31: ...ers 24 V AC The output delivers 24 V DC when the batteries start operating if they are installed 10 11 E 5 Maximum capacity of contacts Device Output Power supply V Power W Accessories 10 11 24 AC DC...

Страница 32: ...ce to resume movement If the contact is not used it must be deactivated during programming 2 Control device NO contact PARTIAL OPENING function PEDESTRIAN OPENING function OPEN ONLY function See funct...

Страница 33: ...t ashes when the operator opens and closes See function F18 additional light 2 Additional light It increases the light in the manoeuvring area See function F18 additional light 3 Operator status warni...

Страница 34: ...and or CY inputs If contacts CX and or CY are not used they must be deactivated during programming DELTA photocells Standard connection DELTA photocells Connection with safety test See function F5 Saf...

Страница 35: ...ut notice Translation of the original instructions DXR photocells Standard connection DXR photocells Connection with safety test See function F5 Safety devices test RX TX 10 11 E 5 10 TS 2 CX CY 10 11...

Страница 36: ...d the keys open and close the gate Getting started Once the electrical connections have been made proceed with commissioning Only skilled and quali ed staff may perform this operation Make sure that t...

Страница 37: ...er C3 appears only if the Automatic closing function is active F3 CY input OFF Default C1 Reopen while closing photocells C2 Reclose while opening photocells C3 Partial stop Only with Automatic close...

Страница 38: ...on active the gate remains idle if the safety devices detect an obstacle The function is active when the gate is closed open or after a complete stop F9 Obstruction detection with motor idle OFF Defau...

Страница 39: ...eypad selector default Thrust Before every opening or closing manoeuvre the leaves thrust inwards to release the electric lock F16 Thrust OFF Default ON Additional light Choose the operating mode of t...

Страница 40: ...time Set the gearmotor working time during opening and closing F22 Operating time 5 to 180 seconds Default 120 M1 opening delay time It adjusts the delay with which the rst leaf must start the openin...

Страница 41: ...sensitivity Adjusting the partial opening In single leaf gates it determines the leaf partial opening percentage with respect to the total travel In two leaf gates it determines the partial opening p...

Страница 42: ...losing approach starting point for M2 percentage of the total travel F44 Closing approach point 1 to 10 Default 10 Number of motors Set the number of motors that control the gate F46 Number of motors...

Страница 43: ...00 bps 4 14400 bps 5 19200 bps 6 38400 bps default 7 57600 bps 8 115200 bps RIO ED T1 Associate one of the available functions with a wireless safety device The function only appears if there is an in...

Страница 44: ...ears if there is an interface board for wireless devices F68 RIO PH T2 OFF Default P1 Reopen while closing P2 Reclose while opening P3 Partial stop Only with Automatic close activated P4 Obstacle stan...

Страница 45: ...ress ENTER to con rm CLr will appear to con rm deletion Remove all Remove all registered users U3 Remove all OFF Default ON Radio decoding Choose the type of radio coding for the transmitters enabled...

Страница 46: ...e gate with the gearmotor connected to M1 N1 If the leaf does not move in the correct direction invert the motor phases A2 Motor test OFF Default ON Travel calibration Start the travel self learning T...

Страница 47: ...during closing E10 Obstacle detected during opening E11 Maximum number of obstacles E14 Serial communication error E15 Incompatible remote control E17 Wireless system communication error E18 Wireless...

Страница 48: ...he contents of this manual may be changed at any time and without notice Translation of the original instructions FINAL OPERATIONS Before closing up the casing check that the cable inlets are sealed t...

Страница 49: ...Page 29 Manual FA01359 EN 03 2021 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 50: ...Page 30 Manual FA01359 EN 03 2021 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 51: ...Page 31 Manual FA01359 EN 03 2021 CAME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions...

Страница 52: ...AME S p A The contents of this manual may be changed at any time and without notice Translation of the original instructions CAME S p A Via Martiri della Libert 15 31030 Dosson di Casier Treviso Italy...

Отзывы: