OCCUPATIONAL SAFETY REGULATIONS

 

In order to guarantee safe mounting, act in keeping with the national regulations on occupational safety 

and accident prevention.

 

 

The guidelines and safety instructions applicable to the installation of electrical devices and 

systems, such as DIN DVE0100-712 for Germany, must be observed.

 

 

 

FIRE  PROTECTION

 

Observe the applicable regulations and safety instructions regarding the fire protection class for 

rooftop installations. The CX product series meet fire class C (Type 6). 

For rooftop mounting, modules must be mounted over a fire resistant roof covering rated for the 

application. The recommended minimum standoff height is 3.25 in (82.55 mm). Modules used in UL 

Listed rooftop applications must be installed with approved mounting systems. If alternate mounting 

means are employed, this may affect the Listing fire class ratings and additional UL fire testing may be 

required. The fire rating of this module is valid only when mounted in the manner specified in the 

mechanical mounting instructions. 

 

 

MECHANICAL ASSEMBLY

 

Only clamp or assembly systems approved by Calyxo (PAS-11-05-0166-EN; PAS-11-05-190EN when 

installing in USA or Canada under UL 1703, respectively) may be installed; otherwise, the extended 

warranty is not void. Calyxo shall test clamp systems upon request and approve them on a case-by-case 

basis. A list of approved clamp systems is available at www.calyxo.com.

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание CX1

Страница 1: ...OPERATING MANUAL CX SERIES REV2 0 May 2017 EN EU USA Canada...

Страница 2: ...S 7 4 MECHANICAL SPECIFICATIONANDDRAWING 10 5 ELECTRICAL SPECIFICATION 11 6 INSTALLATION 12 6 1 MOUNTING 12 6 2 MOUNTING VARIANTS 14 6 3 INSTALLATION SITE MODULE ORIENTATION 15 6 4 AVOIDINGSHADE 16 6...

Страница 3: ...all the following requirements and instructions in order to be able to make full use of the performance capacity of Calyxo solar modules Ensure that the installation operational and maintenance work i...

Страница 4: ...cted to a control device such as an inverter or a chargecontroller Calyxo solar modules are developed and constructed in keeping with the latest technological developments When used properly in accord...

Страница 5: ...ion Physically disconnecting a closed electrical circuit could cause electrical voltage and currents such as electric arcs to arise These could result in life threatening injuries The risk increases w...

Страница 6: ...concentrators such as mirrors or lenses or any other means to artificially concentrate light to increase the power output of the modules Doing so can damage the modules and shall render the extended w...

Страница 7: ...key to safely handling glass is correctly selecting and using personal protective equipment Always ensure your own safety and wear safety goggles safety shoes and cut resistant gloves Gauntlet gloves...

Страница 8: ...revention at constructionsites If you intend to install the modules on a rooftop or at a height observe the specialist regulations set out by the roofing trade Ensure proper fall protection since fall...

Страница 9: ...uest documentation an acceptance report and an inspection report for the PV system with the minimum requirements set out by IEC DIN EN 62446 or VDE 0126 23 from the installer Store these reports toget...

Страница 10: ...iew CX3pro Figure 3 Rear side view CX1 Figure 4 Front side view A CX3 9 0 mm CX3pro 7 0 mm CX1 9 0 mm CX4 7 0 mm Specification CX1 CX3 CX3pro CX4 Length 1200 mm Width 600 mm Weight 12 kg Structure Gla...

Страница 11: ...t Current I sc A 10 Open Circuit Voltage V oc V 10 Current at Maximum Power I mp A 10 Voltage at MaximumPower V mp V 10 Maximum System Voltage 1000V IEC 600V UL Design Load 2400Pa IEC 50lb ft UL STC 1...

Страница 12: ...ditions irradiance of 100 mW cm2 AM 1 5 spectrum and a cell temperature of 25 C 77 F TECHNICAL DATA Additional data including details of the electrical characteristics for the CX series power classes...

Страница 13: ...cture that corresponds to the required statics and the local wind snowloads that can be properly fastened in the ground on the roof or on the facade that can transfer forces on the modules to the asse...

Страница 14: ...lication The recommended minimum standoff height is 3 25 in 82 55 mm Modules used in UL Listed rooftop applications must be installed with approved mounting systems If alternate mounting means are emp...

Страница 15: ...that no direct contact is made between glass and metal Use a suitable silicone free rubber support between the modules andclamps Clamp width figures 7 to 8 70 0 mm A minimum lateral distance between...

Страница 16: ...ny point THEFOLLOWINGMOUNTINGVARIANTSARE POSSIBLE Substructure lateral beneath the module with two clamps per module side figure 7 Substructure diagonal beneath the longer sides with two clamps per mo...

Страница 17: ...is only splash proof Solar modules are not explosion proof equipment Do not install the modules in the proximity of highly flammable gases and vapors such as gas containers petrol stations or near ope...

Страница 18: ...angles of inclination less than3 longitudinal side of the module from the eave it needs to be ensured that adherent contamination is removed by sufficient precipitation or through regular manual clean...

Страница 19: ...dry place The packaging is not weather resistant Ensure that even at low temperatures and or solar radiation of over 1000 W m the maximum open circuit voltage of the wired modules does not exceed the...

Страница 20: ...a module the multiplying factor at conditions of an irradiance of 125 mW cm2 AM 1 5 spectrum and a cell temperature of minus 10 C plus 14 F for VOC and plus 75 C 167 F for ISC is to be determined and...

Страница 21: ...rotected against reverse currents from the rest of the system with a string diode Within the scope of DIN VDE 0100 712 2016 10 diodes are no longer permitted as reverse currentprotection Usually each...

Страница 22: ...ed with the module Install functional grounding for the solar power system when you are installing it in a country or a system in which functional grounding is necessary orprescribed Direct grounding...

Страница 23: ...pro CX4 MC4 connectors of part numbers PV KST4 PV KBT4 CX1 feature MC3 connectors of part numbers PV KST3 PV KBT3 Please note the following when selecting connecting cables and connectors Only use pr...

Страница 24: ...otected from dirt and moisture The connectors are not lying on a water collecting surface and are firmly connected toone another All necessary security and functional inspections have been carried out...

Страница 25: ...te evening Do not wear any conductive pieces or clothing Never enter the installation area alone and without protection We recommend commissioning a specialist company with this work Ask your installe...

Страница 26: ...om the top of the module in the following sequence Rinse off coarse soiling dust foliage etc from the modules with lukewarmwater Moisten stubborn soiling and carefully removeit Use lukewarm water and...

Страница 27: ...cle and environmentally sustainable disposal of electrical and electronic devices is to be understood as a special law under the scope of the general German waste legislation which is laid out in the...

Страница 28: ...information is always accessible and corresponds to the latest status However Calyxo assumes no responsibility for its use or for injuries to patentsor the rights of third parties that may result from...

Страница 29: ...11 Notes...

Отзывы: