INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

MI182 REV.8   Page 1 of 2

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5  Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

MI102 REV.7   Page 6 of 6

F

IG. 

5E - 208 

OR

 240 V

OLT SINGLE PHASE WITHOUT CONTROLS

208 

OU

 240 V

OLT MONOPHASÉ SANS CONTRÔLES

F

IG. 

5F - 208 

OR

 240 V

OLT SINGLE PHASE WITH CONTROLS

208 

OU

 240 V

OLT MONOPHASÉ AVEC CONTRÔLES INCORPORÉS

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5   Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

TM

MI102 REV.7.01  Page 6 of 8

Содержание GX152

Страница 1: ...trol cabinet door Also refer to Fig 5 for typical wiring INSTALLATION AND OPERATING INSTRUCTIONS INSTRUCTIONS D INSTALLATION ET D OP RATION TYPE GX UNIT HEATERS A ROTHERMES ULTRA ROBUSTES MOD LE GX 1...

Страница 2: ...led with proper fast acting fuses or breakers as close as possible to the ratings indicated on the nameplates in compliance with the local electrical codes 4 0 To facilitate mounting the heater has fo...

Страница 3: ...pe 1 enclosure is suitable for dry indoor locations only in non corrosive environments 9 0 For short circuit protection heaters must be installed with proper fast acting fuses or breakers as close as...

Страница 4: ...E NO PHASE L MENT MOTEUR TRANSFORMATEUR 50 VA C CONTACTEUR Bobine 240V VENTAIL Secondaire 240V 3 Required Requis 1 Required Requis GX152 208 3 KXF10008 25 B11085 01 NONE AUCUN C11055 02 GX153 240 1 KX...

Страница 5: ...PERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING During operation take precautions to ensure that combustible materials are always kept at a...

Страница 6: ...L6H 5R5 Tel 905 829 4422 Fax 905 829 4430 www ccithermal com ISO 9001 2000 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING Dur...

Страница 7: ...m the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warra...

Страница 8: ...application inappropri e ou un d faut d alignement des pi ces Aucune garantie ne s applique la finition de peinture except dans le cas de d fauts de fabrication apparen ts dans les 30 jours compter de...

Отзывы: