MI182 REV.8 Page 1 of 2
CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430
www.ccithermal.com
ISO 9001:2000
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR
SERIES OK3 – INFRARED RADIANT HEATERS
FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that
combustible materials are always kept at a safe distance from the radiant energy. This heater is
not intended for use in hazardous areas where flammable vapours, gases or liquids or other
combustibles are present. Remember that objects placed under an infrared heater can take a while
to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended
application, check with the factory for recommendations. Failure to comply can result in personal
injury and/or property damage.
DESCRIPTION
1.0
The OK3 radiant heaters are suitable for comfort heating
use in non-hazardous areas protected from rain, snow or splashing,
where heating element temperatures in excess of 750°C(1382°F)
will not present the risk of fire or explosion. The heater does not
present a safety hazard when it is installed, operated and maintained
in accordance with these instructions.
2.0
The OK3 heater has two U-shaped metal sheath heating
elements factory interconnected in series or parallel depending on
voltage. Never change heaters which have been factory series
connected to a parallel connection.
3.0
Minimum space clearances from combustibles, when
heaters are horizontally mounted and installed, as listed in Table 1
following.
Table 1
Min. Spacing
From nearest wall
600 mm (24”)
From the ceiling
300 mm (12”)
INSTALLATION
The system designer is responsible for
the safety of this equipment and
adequate back-up controls and safety
devices must be installed. Failure to
comply could result in personal injury
and/or property damage.
Heaters must be wired by qualified
personnel in compliance with local
codes.
5.0
Verify that the nameplate voltage and wattage are suitable
for use on the available electrical power supply. Do not connect
the heater to an electrical supply voltage other than shown on the
product label.
Insulation contamination or moisture
accumulation can cause fault to the
element sheath generating arcing and
releasing molten metal. Install proper
ground fault protection to prevent
personal injury and/or property
damage.
6.0
The connection box volume is 3100 cm³(190 in³).
7.0
Supply conductors to the heater must be suitable for
110°C(230°C). The ground wire from the supply shall be connected
to the grounding connection located in the connection box.
8.0
The connection box has eight dual knockouts, ½" or ¾"
and two dual knockouts ¾" or 1". The standard Type 1 enclosure
is suitable for dry, indoor locations only in non-corrosive
environments.
9.0
For short circuit protection, heaters must be installed with
proper fast acting fuses or breakers as close as possible to the
ratings indicated on the nameplates, in compliance with the local
electrical codes.
4.0
To facilitate mounting, the heater has four ¼"-20 mounting
holes located at each top corner of the housing. Either chain
mounting (use eye bolts) or bolting to a non-combustible sliding
support (slotted holes) is adequate provided that the spacing
instructions as given in 3.0 are followed. Chain mounting is preferred
since rigidly mounted heaters are susceptible to warping.
38 cm
[15”]
60 cm
[24”]
30
cm
[12”
]
FIG. 1 – MOUNTING CLEARANCES
MI102 REV.7.01 Page 2 of 8
MI182 REV.8 Page 1 of 2
CCI Thermal Technologies Inc. 2721 Plymouth Drive, Oakville, ON L6H 5R5 Tel. (905) 829-4422 Fax (905) 829-4430
www.ccithermal.com
ISO 9001:2000
INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR
SERIES OK3 – INFRARED RADIANT HEATERS
FIRE/EXPLOSION HAZARD WARNING - During operation, take precautions to ensure that
combustible materials are always kept at a safe distance from the radiant energy. This heater is
not intended for use in hazardous areas where flammable vapours, gases or liquids or other
combustibles are present. Remember that objects placed under an infrared heater can take a while
to reach stabilized temperatures. If you are unsure of the suitability of the heater for the intended
application, check with the factory for recommendations. Failure to comply can result in personal
injury and/or property damage.
DESCRIPTION
1.0
The OK3 radiant heaters are suitable for comfort heating
use in non-hazardous areas protected from rain, snow or splashing,
where heating element temperatures in excess of 750°C(1382°F)
will not present the risk of fire or explosion. The heater does not
present a safety hazard when it is installed, operated and maintained
in accordance with these instructions.
2.0
The OK3 heater has two U-shaped metal sheath heating
elements factory interconnected in series or parallel depending on
voltage. Never change heaters which have been factory series
connected to a parallel connection.
3.0
Minimum space clearances from combustibles, when
heaters are horizontally mounted and installed, as listed in Table 1
following.
Table 1
Min. Spacing
From nearest wall
600 mm (24”)
From the ceiling
300 mm (12”)
INSTALLATION
The system designer is responsible for
the safety of this equipment and
adequate back-up controls and safety
devices must be installed. Failure to
comply could result in personal injury
and/or property damage.
Heaters must be wired by qualified
personnel in compliance with local
codes.
5.0
Verify that the nameplate voltage and wattage are suitable
for use on the available electrical power supply. Do not connect
the heater to an electrical supply voltage other than shown on the
product label.
Insulation contamination or moisture
accumulation can cause fault to the
element sheath generating arcing and
releasing molten metal. Install proper
ground fault protection to prevent
personal injury and/or property
damage.
6.0
The connection box volume is 3100 cm³(190 in³).
7.0
Supply conductors to the heater must be suitable for
110°C(230°C). The ground wire from the supply shall be connected
to the grounding connection located in the connection box.
8.0
The connection box has eight dual knockouts, ½" or ¾"
and two dual knockouts ¾" or 1". The standard Type 1 enclosure
is suitable for dry, indoor locations only in non-corrosive
environments.
9.0
For short circuit protection, heaters must be installed with
proper fast acting fuses or breakers as close as possible to the
ratings indicated on the nameplates, in compliance with the local
electrical codes.
4.0
To facilitate mounting, the heater has four ¼"-20 mounting
holes located at each top corner of the housing. Either chain
mounting (use eye bolts) or bolting to a non-combustible sliding
support (slotted holes) is adequate provided that the spacing
instructions as given in 3.0 are followed. Chain mounting is preferred
since rigidly mounted heaters are susceptible to warping.
38 cm
[15”]
60 cm
[24”]
30
cm
[12”
]
FIG. 1 – MOUNTING CLEARANCES
3.7
MOTOR ROTATION - IMPORTANT. Three phase heaters are
supplied with motors of corresponding phase. The proper motor/fan
rotation, viewed from the rear of the heater is counter clockwise,
incorrect rotation of the fan will cause the heater to overheat and
cycle on the high limit. To reverse the fan rotation, interchange two
supply voltage conductors connected to lugs L1, L2.
3.8
The schematic wiring diagram in Fig. 5 illustrates the GX unit
heater with contactor, transformer and thermostat. Some of this
equipment is optional and may not be included with your GX heater.
4.0 TEMPERATURE CONTROL
4.1
BUILT-IN THERMOSTAT - heaters with a factory installed
thermostat have all other standard controls such as contactors,
and transformers factory installed and prewired.
4.2
THERMOSTAT KIT FAT-8A - (Field installed) Install the FAT-8A
thermostat kit in accordance with the instruction sheet provided.
4.3
REMOTE LINE VOLTAGE THERMOSTAT - A remote
thermostat rated to operate as a pilot duty, inductive device on
240V is required. For proper installation and wiring of the selected
thermostat, refer to the manufacturer’s instructions. CCI Thermal
Technologies can supply appropriate thermostats.
4.4
REMOTE LOW VOLTAGE THERMOSTATS - The GX heater
can be provided with a low voltage control internally wired for
remote connection to 24V thermostats. Ensure that this control
option is installed in the GX heater before energizing a low voltage
thermostat from the heater. For proper installation and wiring of the
selected thermostat, refer to the manufacturer’s instructions. CCI
Thermal Technologies can supply low voltage thermostats for use
with GX heaters.
5.0
“FAN ONLY”
FEATURE (Summer Switch)
The “fan only” feature will allow the heater to cycle in a “heat”
mode dictated by the controlling thermostat, even though the fan is
operating continuously.
5.1
Terminals are provided for remote mount of a S.P.S.T.
“fan only”
switch, rated 240V 60Hz. A jumper across terminals “T2” and “T3”
is installed at the factory, and must be removed and substituted
with the remote switch leads if this feature is to be available. See
Fig. 5.
5.2
A
“fan only”
switch may be factory installed (optional extra)
directly in the heater.
6.0 FAN DELAY
All GX unit heaters incorporate a fan delay feature in both the “ON”
and
“OFF”
cycles. This is a desirable feature allowing the heater
to come to temperature before the fan operates (no cold blasts)
and to cool down in the
“OFF”
cycle (longer life for the control
components and motor). Delay “ON” is 20-50 seconds and delay
“OFF”
is 20-70 seconds.
7.0 REMOTE ENERGY MANAGEMENT CONTROL
Remote energy management control is standard on 40 and 50kW
units. Internal power to contactor coil C2 may be interrupted and
controlled remotely by removing the jumper between terminals
“T2” and “T3”, and then connecting a passive contactor in its place.
A closed contact will allow 100% heating capacity and an open
contact will allow 50% heating capacity. See schematic wiring
diagram Fig. 5.
3.7
ROTATION DU MOTEUR - IMPORTANT. Sur tous les appareils
triphasés, les moteurs sont également triphasés. Vue de l’arrière
de l’appareil, la rotation normale de l’éventail est dans le sens
anti-horaire. Une rotation inversée entrainera l’arrêt de l’appareil
par la haute-limite. Pour corriger la rotation, interchangez deux fils
d’alimentation sur les cosses L1, L2.
3.8
Le schéme de la Fig. 5 illustre un appareil GX muni d’un
contacteur, transformateur et thermostat. Cet équipement est
facultatif et peut ne pas être inclus dans votre appareil.
4.0 CONTRÔLE DE TEMPÉRATURE
4.1
THERMOSTAT INTÉGRÉ - Les appareils avec thermostat
intégré possède tous les autres contrôles tels que contacteur et
transformateur et sont préfilés en usine.
4.2
TROUSSE DE THERMOSTAT FAT -8A - (Pour installation
en chantier) Installez le thermostat FAT-8A selon les instructions
fournies avec cette trousse.
4.3
THERMOSTAT À TENSION SECTEUR À DISTANCE - Un
thermostat à distance, adéquat pour circuit de commande et appareil
inductif à 240V ets requis. Voir les instructions du manufacturier
pour une installation adéquate. CCI Thermal Technologies
possède en magasin une gamme variée de thermostats.
4.4
THERMOSTAT À BASSE TENSION À DISTANCE - L’appareil
GX peut intégré les contrôles requis pour le raccordement à
distance d’un thermostat à 24V. Assurez-vous que ce dispositif
facultatif est intégré à l’appareil GX avant d’opérer un thermostat
à basse tension à partir de l’appareil. Voir les instructions du
manufacturier pour une installation adéquate. CCI Thermal
Technologies possèdent une gamme variée de thermostats à
basse tension.
5.0 COMMANDE DU VENTILATEUR (Interrupteur Estival)
Cette caractéristique permet à l’appareil de répondre à l’appel de
chauffage, même si l’éventail est en opération continue.
5.1
Un bornier est prévu pour l’installation à distance d’un
interrupteur du ventilateur (U.P.U.D.), 240V 60Hz. Un cavalier
est instalé en usine entre les bornes T2 et T3, lequel sera
enlevé et substitué par les fils de l’interrupteur à distance si cette
caractéristique doit être disponible. Voir Fig. 5.
5.2 Un interrupteur du ventilateur est disponible pour l’installation
intégrée en usine (facultatif moyennant un suppliment).
6.0 COMMANDE À RETARDEMENT DU VENTILATEUR
Tous les appareils GX sont munis d’une commande à retardement
du ventilateur pour la mise en marche et l’arrêt. Cette caractéristique
unique évite la projection d’air froid au démarrage et la surchauffe
à l’arrêt, d’où une meilleure durabilité des composants de contrôles
et du moteur. Le délai de mise en “marche” est de 20-50 secondes
et le délai “d’arrêt” est de 20-70 secondes.
7.0 RÉGUALTEUR CENTRAL D’ÉNERGIE À DISTANCE
Des borniers intégrés à tous les appareils de 40 et 50kW permettent
d’interrompre la puissance au contacteur C2. En enlevant le
cavalier T2, T3 à bobine du contacteur C2 et en le substituant par
un contact passif, vous réduirez do 50% la capacité de l’appareil
selon le signal de la position ouverte ou fermée commandée par le
régulateur central d’énergie à distance. Voir schéma Fig. 5.