background image

MI182 REV.8   Page 1 of 2

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5  Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

MI102 REV.7.01  Page 2 of 8

MI182 REV.8   Page 1 of 2

CCI Thermal Technologies Inc.  2721 Plymouth Drive, Oakville, ON L6H 5R5  Tel. (905) 829-4422  Fax (905) 829-4430

www.ccithermal.com

ISO 9001:2000

INSTALLATION, OPERATION AND MAINTENANCE INSTRUCTIONS FOR

SERIES OK3  –  INFRARED RADIANT HEATERS

FIRE/EXPLOSION  HAZARD  WARNING  -  During  operation,  take  precautions  to  ensure  that

combustible materials are always kept at a safe distance from the radiant energy.  This heater is

not  intended  for  use  in  hazardous  areas  where  flammable  vapours,  gases  or  liquids  or  other

combustibles are present.  Remember that objects placed under an infrared heater can take a while

to reach stabilized temperatures.  If you are unsure of the suitability of the heater for the intended

application, check with the factory for recommendations.  Failure to comply can result in personal

injury and/or property damage.

DESCRIPTION

1.0

The OK3 radiant heaters are suitable for comfort heating

use in non-hazardous areas protected from rain, snow or splashing,

where heating element temperatures in excess of 750°C(1382°F)

will not present the risk of fire or explosion.  The heater does not

present a safety hazard when it is installed, operated and maintained

in accordance with these instructions.

2.0

The OK3 heater has two U-shaped metal sheath heating

elements factory interconnected in series or parallel depending on

voltage.  Never change heaters which have been factory series

connected to a parallel connection.

3.0

Minimum  space  clearances  from  combustibles,  when

heaters are horizontally mounted and installed, as listed in Table 1

following.

Table 1

Min. Spacing

From nearest wall

600 mm (24”)

From the ceiling

300 mm (12”)

INSTALLATION

The system designer is responsible for

the  safety  of  this  equipment  and

adequate back-up controls and safety

devices must be installed.  Failure to

comply could result in personal injury

and/or property damage.

Heaters  must  be  wired  by  qualified

personnel  in  compliance  with  local

codes.

5.0

Verify that the nameplate voltage and wattage are suitable

for use on the available electrical power supply.  Do not connect

the heater to an electrical supply voltage other than shown on the

product label.

Insulation  contamination  or  moisture

accumulation  can  cause  fault  to  the

element sheath generating arcing and

releasing molten metal.  Install proper

ground  fault  protection  to  prevent

personal  injury  and/or  property

damage.

6.0

The connection box volume is 3100 cm³(190 in³).

7.0

Supply  conductors  to  the  heater  must  be  suitable  for

110°C(230°C).  The ground wire from the supply shall be connected

to the grounding connection located in the connection box.

8.0

The connection box has eight dual knockouts, ½" or ¾"

and two dual knockouts ¾" or 1".  The standard Type 1 enclosure

is  suitable  for  dry,  indoor  locations  only  in  non-corrosive

environments.

9.0

For short circuit protection, heaters must be installed with

proper fast acting fuses or breakers as close as possible to the

ratings indicated on the nameplates, in compliance with the local

electrical codes.

4.0

To facilitate mounting, the heater has four ¼"-20 mounting

holes  located  at  each  top  corner  of  the  housing.  Either  chain

mounting (use eye bolts) or bolting to a non-combustible sliding

support  (slotted  holes)  is  adequate  provided  that  the  spacing

instructions as given in 3.0 are followed.  Chain mounting is preferred

since rigidly mounted heaters are susceptible to warping.

38 cm

[15”]

60 cm

[24”]

30

 cm

[12”

]

FIG. 1  –  MOUNTING CLEARANCES

3.7

 MOTOR ROTATION - IMPORTANT. Three phase heaters are 

supplied with motors of corresponding phase. The proper motor/fan 

rotation, viewed from the rear of the heater is counter clockwise, 

incorrect rotation of the fan will cause the heater to overheat and 

cycle on the high limit. To reverse the fan rotation, interchange two 

supply voltage conductors connected to lugs L1, L2.

3.8

 The schematic wiring diagram in Fig. 5 illustrates the GX unit 

heater with contactor, transformer and thermostat. Some of this 

equipment is optional and may not be included with your GX heater.

4.0 TEMPERATURE CONTROL
4.1

 BUILT-IN THERMOSTAT - heaters with a factory installed 

thermostat have all other standard controls such as contactors, 

and transformers factory installed and prewired.

4.2

 THERMOSTAT KIT FAT-8A - (Field installed) Install the FAT-8A 

thermostat kit in accordance with the instruction sheet provided.

4.3

 REMOTE LINE VOLTAGE THERMOSTAT - A remote 

thermostat rated to operate as a pilot duty, inductive device on 

240V is required. For proper installation and wiring of the selected

thermostat, refer to the manufacturer’s instructions. CCI Thermal 

Technologies can supply appropriate thermostats.

4.4

 REMOTE LOW VOLTAGE THERMOSTATS - The GX heater 

can be provided with a low voltage control internally wired for 

remote connection to 24V thermostats. Ensure that this control 

option is installed in the GX heater before energizing a low voltage 

thermostat from the heater. For proper installation and wiring of the 

selected thermostat, refer to the manufacturer’s instructions. CCI 

Thermal Technologies can supply low voltage thermostats for use 

with GX heaters.

5.0

 “FAN ONLY”

 

FEATURE (Summer Switch) 

The “fan only” feature will allow the heater to cycle in a “heat” 

mode dictated by the controlling thermostat, even though the fan is 

operating continuously.

5.1

 Terminals are provided for remote mount of a S.P.S.T. 

“fan only” 

switch, rated 240V 60Hz. A jumper across terminals “T2” and “T3” 

is installed at the factory, and must be removed and substituted 

with the remote switch leads if this feature is to be available. See 

Fig. 5.

5.2

 A 

“fan only” 

switch may be factory installed (optional extra) 

directly in the heater.

6.0 FAN DELAY

All GX unit heaters incorporate a fan delay feature in both the “ON”

and 

“OFF”

 cycles. This is a desirable feature allowing the heater 

to come to temperature before the fan operates (no cold blasts) 

and to cool down in the 

“OFF”

 cycle (longer life for the control 

components and motor). Delay “ON” is 20-50 seconds and delay 

“OFF”

 is 20-70 seconds.

7.0 REMOTE ENERGY MANAGEMENT CONTROL

Remote energy management control is standard on 40 and 50kW 

units. Internal power to contactor coil C2 may be interrupted and 

controlled remotely by removing the jumper between terminals 

“T2” and “T3”, and then connecting a passive contactor in its place. 

A closed contact will allow 100% heating capacity and an open 

contact will allow 50% heating capacity. See schematic wiring 

diagram Fig. 5.

3.7

 ROTATION DU MOTEUR - IMPORTANT. Sur tous les appareils 

triphasés, les moteurs sont également triphasés. Vue de l’arrière 

de l’appareil, la rotation normale de l’éventail est dans le sens 

anti-horaire. Une rotation inversée entrainera l’arrêt de l’appareil 

par la haute-limite. Pour corriger la rotation, interchangez deux fils 

d’alimentation sur les cosses L1, L2.

3.8

 Le schéme de la Fig. 5 illustre un appareil GX muni d’un 

contacteur,  transformateur  et  thermostat.  Cet  équipement  est 

facultatif et peut ne pas être inclus dans votre appareil.

4.0 CONTRÔLE DE TEMPÉRATURE
4.1

 THERMOSTAT INTÉGRÉ - Les appareils avec thermostat 

intégré possède tous les autres contrôles tels que contacteur et 

transformateur et sont préfilés en usine.

4.2

 TROUSSE DE THERMOSTAT FAT -8A - (Pour installation 

en chantier) Installez le thermostat FAT-8A selon les instructions 

fournies avec cette trousse.

4.3

 THERMOSTAT À TENSION SECTEUR À DISTANCE - Un 

thermostat à distance, adéquat pour circuit de commande et appareil 

inductif à 240V ets requis. Voir les instructions du manufacturier 

pour  une  installation  adéquate.  CCI  Thermal  Technologies 

possède en magasin une gamme variée de thermostats.

4.4 

THERMOSTAT À BASSE TENSION À DISTANCE - L’appareil 

GX  peut  intégré  les  contrôles  requis  pour  le  raccordement  à 

distance  d’un  thermostat  à  24V. Assurez-vous  que  ce  dispositif 

facultatif est intégré à l’appareil GX avant d’opérer un thermostat 

à basse tension à partir de l’appareil. Voir les instructions du 

manufacturier  pour  une  installation  adéquate.  CCI  Thermal 

Technologies possèdent une gamme variée de thermostats à 

basse tension.

5.0 COMMANDE DU VENTILATEUR (Interrupteur Estival) 

Cette caractéristique permet à l’appareil de répondre à l’appel de 

chauffage, même si l’éventail est en opération continue. 

5.1

 Un bornier est prévu pour l’installation à distance d’un 

interrupteur du ventilateur (U.P.U.D.), 240V 60Hz. Un cavalier 

est  instalé  en  usine  entre  les  bornes  T2  et  T3,  lequel  sera 

enlevé et substitué par les fils de l’interrupteur à distance si cette 

caractéristique doit être disponible. Voir Fig. 5.

5.2 Un interrupteur du ventilateur est disponible pour l’installation 

intégrée en usine (facultatif moyennant un suppliment).

6.0 COMMANDE À RETARDEMENT DU VENTILATEUR

Tous les appareils GX sont munis d’une commande à retardement

du ventilateur pour la mise en marche et l’arrêt. Cette caractéristique

unique évite la projection d’air froid au démarrage et la surchauffe

à l’arrêt, d’où une meilleure durabilité des composants de contrôles

et du moteur. Le délai de mise en “marche” est de 20-50 secondes

et le délai “d’arrêt” est de 20-70 secondes.

7.0 RÉGUALTEUR CENTRAL D’ÉNERGIE À DISTANCE

Des borniers intégrés à tous les appareils de 40 et 50kW permettent

d’interrompre la puissance au contacteur C2. En enlevant le  

cavalier T2, T3 à bobine du contacteur C2 et en le substituant par 

un contact passif, vous réduirez do 50% la capacité de l’appareil 

selon le signal de la position ouverte ou fermée commandée par le 

régulateur central d’énergie à distance. Voir schéma Fig. 5.

Содержание GX152

Страница 1: ...trol cabinet door Also refer to Fig 5 for typical wiring INSTALLATION AND OPERATING INSTRUCTIONS INSTRUCTIONS D INSTALLATION ET D OP RATION TYPE GX UNIT HEATERS A ROTHERMES ULTRA ROBUSTES MOD LE GX 1...

Страница 2: ...led with proper fast acting fuses or breakers as close as possible to the ratings indicated on the nameplates in compliance with the local electrical codes 4 0 To facilitate mounting the heater has fo...

Страница 3: ...pe 1 enclosure is suitable for dry indoor locations only in non corrosive environments 9 0 For short circuit protection heaters must be installed with proper fast acting fuses or breakers as close as...

Страница 4: ...E NO PHASE L MENT MOTEUR TRANSFORMATEUR 50 VA C CONTACTEUR Bobine 240V VENTAIL Secondaire 240V 3 Required Requis 1 Required Requis GX152 208 3 KXF10008 25 B11085 01 NONE AUCUN C11055 02 GX153 240 1 KX...

Страница 5: ...PERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING During operation take precautions to ensure that combustible materials are always kept at a...

Страница 6: ...L6H 5R5 Tel 905 829 4422 Fax 905 829 4430 www ccithermal com ISO 9001 2000 INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES OK3 INFRARED RADIANT HEATERS FIRE EXPLOSION HAZARD WARNING Dur...

Страница 7: ...m the date of installation The Company neither assumes nor authorizes any person to assume for it any other obligation or liability in connection with the product s The Purchaser agrees that all warra...

Страница 8: ...application inappropri e ou un d faut d alignement des pi ces Aucune garantie ne s applique la finition de peinture except dans le cas de d fauts de fabrication apparen ts dans les 30 jours compter de...

Отзывы: