on the 1142RX master. The higher the better but a minimum of 55 is recommended to give a 
reliable signal. To cancel each call press both buttons at the same time on the transmitter unit. 
 
Repeat this process until all the units have been tested. There is no need to action anything at 
the 1142RX master as each time a Call alert button is tested it updates the RSSI value.  
 
It is sensible to keep a record of this test so that should there be difficulties with receiving  signals 
from all the units above the 55 RSSI 

value you will able to “Map” how the signal is propagat

ing 

through the building.  
 
If you cannot setup the system due to low signals please contact Call Aid UK on 0115 940 0905 
for technical assistance. 
 
To exit the RSSI mode press the RSSI button once again. 
 

RSSI

TEST 
MODE

UP

DOWN

NIGHT

MUTE

 

 

 

1142RX 

Engineer’s Menu

 

 Schematic 

 

Содержание 1142RX

Страница 1: ...Radio System 1142 Radio Portable Manual O M Manual V6 docx Page 1 of 20 1142RX Portable Radio Duress Alarm System Operation Maintenance Manual Call Aid UK Ltd Unit 5 Factory Lane Beeston Nottingham U...

Страница 2: ...he radio Call alert buttons can transmit to the 1142RX receiver 1142RX Incoming Alerts When a call button is pressed the 1142RX display panel will respond by showing the call unit identity in the OLED...

Страница 3: ...A MANUALS INSTRUCTIONS 2017 1142 Radio System 1142 Radio Portable Manual O M Manual V6 docx Page 3 of 20 240 volt socket Battery charger 1142RX Portable Master Display Panel Call Aid UK 1142 radio Bas...

Страница 4: ...any cancel signal is sent from a portable Call alert button the battery level is sent at the same time After the call has been cancelled should the battery be running low a Low battery message will b...

Страница 5: ...ower for a short time when the button is pressed To access the batteries remove the small screw on the rear of the portable Call alert button and replace the old battery with the new one Please ensure...

Страница 6: ...he battery It should not be allowed to run flat Call Panic Buttons for this System continued 1115 Pendant Wrist Strap panic button The 1115 panic button is a battery powered unit that as standard will...

Страница 7: ...ssing the GREEN button will send an assist call signal to the 1142 master which will display the identity of the call alert button and a low level audio alert Pressing the RED button on the wall unit...

Страница 8: ...an orange pull cord and triangle Cancelling at source To cancel an alert at the call unit press and hold both buttons The reassurance lights will stop flashing and the alert will have cleared from th...

Страница 9: ...d There is no need to action anything at the 1142RX master as each time a Call alert button is tested it updates the RSSI value It is sensible to keep a record of this test so that should there be dif...

Страница 10: ...142 Radio System 1142 Radio Portable Manual O M Manual V6 docx Page 10 of 20 System ID 0 7 Display No 0 99 Cancel Source Cancel Panel Night M _Global _Local PPB Mode Fixed Locate Mute Time 0 600 Secon...

Страница 11: ...Source Panel Cancel Method Selecting Cancel Calls can be set to be cancelled at the unit from which the Call alert was sent SOURCE Please refer to specific unit instruction Calls can be set to be canc...

Страница 12: ...s set the MUTE will be overridden Relay Output Type The 1142RX has an output that can be used with the CAUK 1132 Relay PCB This output can be used to control external sounders or interface with third...

Страница 13: ...fixing Hold the unit in the proposed position and test by putting a call to the radio receiver Try not to cover the 1150 with the hand as this will adversely affect the range Low Battery Setting room...

Страница 14: ...screws Remove the two screws and the back box will be free to be installed To fit the 1124 back to the surface box fasten with the two 3 5mm screws supplied these are the correct length clip in the d...

Страница 15: ...s to be added or removed see picture below for the header to use If the header is fitted a low level call is transmitted if the header is not fitted a high level call is transmitted Changing the batte...

Страница 16: ...1142 Radio Portable Manual O M Manual V6 Z AA MANUALS INSTRUCTIONS 2017 1142 Radio System 1142 Radio Portable Manual O M Manual V6 docx Page 16 of 20 1123 Radio Signal Repeater...

Страница 17: ...e of the 1123 IP65 Repeater there are few place for making holes that will allow the repeater unit to be screwed onto the wall Before the repeater is screwed to the wall test that all the Call alert b...

Страница 18: ...ic buttons are pressed the 1123 unit will begin to flash and a low volume tone will sound the low volume is for the personnel nearby to hear but not the person in the room who is causing the incident...

Страница 19: ...tton on the pendant or activate any other device that needs to be paired to this unit the bottom left hand red lamp will flash twice to confirm the pairing and a beep will sound if a buzzer is fitted...

Страница 20: ...in the vicinity The 1123 also acts as a repeater sending messages on to the master panel When any panic buttons are pressed the 1123 unit will begin to flash and a tone will sound To silence the 1123...

Страница 21: ...l over door lamp will flash and beep every 5 minutes to warn the users The low battery alert can be removed by replacing the battery in the call panic unit Relay connections please note that if ground...

Отзывы: