8.3.3
Overload Light is On
CAUSE
SOLUTION
Unit is overloaded
Remove overload or check CL setting
Unit is switched to high voltage range.
Select correct voltage range.
8.3.4
Distorted Output
CAUSE
SOLUTION
Power source is grossly overloaded.
Reduce load
The crest factor of the load exceeds 3:1 on the
low range or 5:1 on the high range.
Reduce load current peaks by reducing load.
8.3.5
Unit Shuts Down after 1-2 Seconds
CAUSE
SOLUTION
Output shorted
Remove output short
Output grossly overloaded.
Remove overload.
PFC IGBT module failure
Have power module serviced
Operating load with too high inrush or start up
currents.
Consult factory for application advice.
8.3.6
No Output and No Lights on Front Panel
CAUSE
SOLUTION
Input circuit breaker switched off.
Switch the breaker on.
No input power to F1 – F3 or F1 - F6 (model
dependent).
Ensure 3 phase power is getting to input fuses.
LV Power Supply failure
Have LV supply serviced.
8.3.7
No Output But Front Panel controller is active
CAUSE
SOLUTION
“OUTPUT ON” button is turned off.
Press OUTPUT ON so that “ON” LED is lit.
REMOTE INHIBIT pins 5 & 6 at TB3 on rear
panel are shorted together.
Check polarity setting or RI Mode. Use
OUTPut:RI[:LEVel] LOW/HIGH command
to set RI mode to high or low.
Current limit programmed down or to zero.
Program current limit higher.
Voltage programmed down or to zero.
Turn amplitude control up.
Содержание BPS Series
Страница 1: ...M440077 01 Rev A www programmablepower com BPS Series AC Power Source User Manual...
Страница 26: ...AMETEK Programmable Power BPS Series User Manual M440077 01 Rev A 26...
Страница 36: ...AMETEK Programmable Power BPS Series User Manual M440077 01 Rev A 36 Figure 4 1 BPS75 BPS90 Power Source Photo...
Страница 111: ...User Manual AMETEK Programmable Power BPS Series 111 Figure 6 2 BPS90 Series Detailed Block Diagram...
Страница 112: ...User Manual AMETEK Programmable Power BPS Series 112 Figure 6 3 Power Module Detailed Block Diagram...
Страница 114: ...User Manual AMETEK Programmable Power BPS Series 114 Figure 6 4 Power Module Layout...