SATK40 & Procyl

®

9

Operating Cycles

Domestic water generation: 

When a tap or shower is turned on the domestic water cycle is
activated, due to the storage thermostat intervention.

To restore the temperature of the stored water in the cylinder
the unit begins repeated 10 minute cycles. 

After the first 10 minute cycle has been completed a second
cycle begins again supplying only the cylinder with heat
followed by a third or fourth until the water in the cylinder has
reached the set temperature.

To enable the division of the 10 minute cycle, to apportion the
time for heating and DHW, dip switch 5 needs to be on. 

By altering P1 a portion of each 10 minute can be directed to
the space heating circuit, for example 9 minutes to the cylinder
and 1 minute to the heating circuit or 7 minutes to the cylinder
and 3 minutes to the heating circuit.

When the specified domestic hot water temperature is reached,
the circulation pump switches off and the modulating valve is
closed again.

The domestic water cycle, when active, is indicated by the
steady yellow DHW LED while the symbol is blinking.

The temperature of the hot domestic water within the indirect
cylinder should be set using the cylinder thermostat (only
supplied with the Procyl

®

option).

Heating cycle:  Set point regulation

When space heating is requested by the room thermostat, the
circulation pump is powered while the modulating valve is
opened gradually until the set point temperature is reached.

At the end of the heating cycle, the circulation pump comes to
a stop and the modulating valve is closed.

The active heating cycle is signalled by the yellow CH LED
which comes on.

The heating cycle temperature set point can be set using
trimmer P2 and shown on the display.

Under floor heating function: at LOW temperature setting

This cycle aids the drying of the underfloor heating screed at
low temperatures. This function can only be activated and
executed if there are no faults

It can be activated by pressing and holding the RESET button
for 8 seconds.

The yellow CH LED blinks while the under floor heating drying
function is in operation.

The function has a duration of 240 hours, and is carried out by
simulating a request to run in heating mode starting from a set
point of 25°˚C and rising in regular intervals to a temperature
of 45˚C.

Once the maximum set point has been reached, the function is
executed, following the same procedures, in reverse (from the
maximum set point to the minimum set point).

This function has priority over heating and hot water cycles,
and can be suspended at any time by pressing and holding the
RESET button for 8 seconds.

Optional functions

- to activate/deactivate the optional

functions the electric power supply must always be turned off.

Operating Cycles

25

8 seconds

60

P2

P1

––

P2

P1

ON

1

2

3

5

6

4

Содержание Altecnic SATK40103

Страница 1: ...SATK40 Procyl heat interface unit Installation Operation Maintenance Instructions...

Страница 2: ...tures higher than 50 C may cause severe burns When installing commissioning and maintaining the device take the necessary precautions so that these temperatures will not be hazardous for people Conten...

Страница 3: ...t off the electric supply before opening the HIU cover 1 During installation and maintenance operations always avoid direct contact with live or potentially hazardous parts 2 The device must not be ex...

Страница 4: ...he position of the water pipe connections Check the measurements again before installing pipework and electrical cables Hydraulic connections 1 connection to the pipework from the centralised boiler p...

Страница 5: ...ve earthing system constructed as speci ed in current safety regulations This is a compulsory safety requirement Connection to the main supply The device is supplied with an electric supply cable plug...

Страница 6: ...repeat the lling process if necessary Fitting the cover Place the casing over the frame inserting the upper tabs 1 into the corresponding slots 2 Place the lower part of the casing over the frame Tig...

Страница 7: ...circuit pressure switch fault Error code 4 The SATK40 HIU continuously monitors the pressure in the apartments secondary heating circuit If the pressure falls in this circuit the pressure switch is a...

Страница 8: ...power failure the thermal safety valve prevents hot water for heating purposes from entering the system After the user has reset the isolation imposed by the safety thermostat the shut off valve can...

Страница 9: ...e setting 25 to 45 C MEDIUM HIGH temperature setting 50 to 75 C Optional functions Heating cycle modulating temperature regulation with compensated set point floor slab heating function Factory settin...

Страница 10: ...is requested by the room thermostat the circulation pump is powered while the modulating valve is opened gradually until the set point temperature is reached At the end of the heating cycle the circu...

Страница 11: ...etter ef ciency and helps to save energy Before carrying out any maintenance repair or part replacement work proceed as follows Switch off the electric supply Remove the cover Close the shut off valve...

Страница 12: ...cting the connector see page 16 Unscrew the probe Fit the new probe Reconnect the connector respecting the only possible way it can be inserted Expansion vessel pre charge check For the system to work...

Страница 13: ...lay Fused Switch 21 22 6 7 10 11 1 2 3 4 2 5 Com N SL L N E HW On 1 2 3 8 4 CH On 8 9 9 2 10 11 1 2 3 L N E Wiring Centre 7 8 9 10 11 1 2 3 4 5 6 5 2 6 7 L N Br Bl Gr Or Not supplied wiring to be made...

Страница 14: ...i ed personnel to have it replaced electronic controller not working call quali ed personnel to have it replaced all LEDs are off electricity power supply switched off switch on electricity supply pro...

Страница 15: ...faulty call quali ed personnel to have it replaced presence of air in the system vent the system pump not working call quali ed personnel to have it replaced pump cable not connected restore connecti...

Страница 16: ...ecnic co uk IOM 033 23 10 15 E O E Notes In these Installation Operation and Maintenance Instructions we have endeavoured to make the information as accurate as possible We cannot accept any responsib...

Отзывы: