Installation

Indications,

 functions and options

Operation and function

en

System 2 (weather-compensated heating – flow temperature controlled cooling)

R2 = open
R3 = closed

Flow

Return

R1

S2

S1

The controller monitors the room thermostat (TA).
If the room thermostat demands heat, the pump (R1) starts and R4 is energised for 
the heating demand. The temperature at S2 is monitored. 
The controller calculates the set flow temperature by means of the outdoor tem-
perature (S1) and the selected heating curve. The mixer is controlled so that the 
calculated set flow temperature is reached and maintained at S2.
The controller is equipped with a non-adjustable safety shutdown function. If the 
temperature at S2 reaches or exceeds 90 °C, the mixer closes. The warning symbol 

 appears on the screen and the Lightwheel

®

 flashes yellow. If the temperature 

at S2 reaches or exceeds 95 °C,R1 and R4 switch off. The Lightwheel

®

 flashes red.

If theTMax  option  is  activated,  the  value  for  the  safety  shutown  function  can  be 
reduced. If the temperature at S2 exceeds TMax by less than 5K, the warning symbol 

 appears on the screen and the Lightwheel

®

 flashes yellow. If the temperature at S2 

exceeds TMax by more than 5 K, R1 and R4 switch off. The Lightwheel

®

 flashes red.

If the Cooling  option  is  activated,  the  mixer  is  controlled  so  that  the  adjusted 
cooling temperature TCool is reached and maintained at S2. The S7 contact can be 
used for connecting a switch for remotely controlling the heating / cooling mode. 
Contact open = cooling mode
Contact closed = heating mode 

If the Condensation  option  is  activated,  the  controller  monitors  a  dew  point 
switch.  If  the  dew  point  switch  triggers  an  alarm,  cooling  stops  and  the  warning 
symbol is indicated.
Terminal allocation
S1 

=  outdoor temperature sensor

S2 

=  heating circuit flow

S3/RTA12 =  return sensor or remote control (optional)
TA 

=  room thermostat

S5/TS10  =  dew point switch (optional)
S6 

=  RPS Grundfos Direct Sensor™ pressure sensor (optional)

S7 

=  contact for remotely controlling the heating / cooling mode (optional)

R1 

= pump

R2 

=  mixer open

R3 

=  mixer closed

R4 

=  demand contact of the heat generator (potential-free extra-low volt-

age relay). If the voltage at the contact used is higher than 30 V, use the 
auxiliary terminals at the 230 V side for the mixer.

PWM 1  =  R1 speed signal, profile selectable

Adjustment and balance values menu system 2

Factory 
setting 

Range

Description

System

1

1, 2

System selection

Curve

0.8

0.3 … 3.0

Heating curve

TMin

Yes

Yes, No

Minimum temperature heating circuit option

TMin

25 °C

15 °C … 40 °C

Minimum temperature heating circuit

TMax

Yes

Yes, No

Maximum temperature heating circuit option

TMax

50 °C

30 °C … 90 °C

Maximum temperature heating circuit

Remote control No

Yes, No

Remote control option

Cooling

No

Yes, No

Cooling option

TCool

16 °C

5 °C … 25 °C

Cooling temperature

Condensat.

Yes

Yes, No

Dew point switch (DPS) option

Chiller on

No

Yes, No

Cooling demand on option

Pressure

No

Yes, No

Low pressure monitoring option

PMin

0.6 bar

0.2  … 10.0 bar

Switch-on threshold low pressure monitoring

tMixer

75 s

30 … 240 s

Mixer runtime

Содержание 161010

Страница 1: ...nce from this unit Please keep this manual safe Manual en Heating controller Manual for the specialised craftsman Installation Operation Troubleshooting Digital controller with system representation 1...

Страница 2: ...tem are not exposed to strong electromagnetic fields Subject to technical change Errors excepted Target group These instructions are exclusively addressed to authorised skilled personnel Only qualifie...

Страница 3: ...allation 5 2 1 Mounting 5 2 2 Electrical connection 5 3 Operation and function 6 3 1 Buttons and adjustment dial 6 3 2 Adjustment values and user code 6 3 3 Control LED 7 4 Systems 7 5 Indications fun...

Страница 4: ...acity 4 A 240V Power supply 100 240V 50 60 Hz Supply connection typeY attachment Power consumption 1 W Mode of operation type 1 B C Y action Rated impulse voltage 2 5 kV Data interface VBus VBus curre...

Страница 5: ...ning screw 2 2 Electrical connection WARNING Electric shock Upon opening the housing live parts are exposed Always disconnect the device from power supply before opening the housing ATTENTION ESD dama...

Страница 6: ...ng the device to the mains Note The connection depends on the system layout selected see page 7 The auxiliary terminals can be used instead of R4 as the mixer switch for the heat generator if a voltag...

Страница 7: ...ipped with a non adjustable safety shutdown function If the temperature at S2 reaches or exceeds 90 C the mixer closes The warning symbol appears on the screen and the Lightwheel flashes yellow If the...

Страница 8: ...pressure monitoring tMixer 75 s 30 240 s Mixer runtime Corr tMixer 90 s 5 300 s Surplus mixer runtime when the mixer is closing tPLAY 4 s 1 15 s Mixer control time for change of flow direction Block...

Страница 9: ...a switch for remotely controlling the heating cooling mode Contact open cooling mode Contact closed heating mode If the Condensation option is activated the controller monitors a dew point switch If t...

Страница 10: ...lock prot Yes Yes No Blocking protection option PWM Heating Heating Solar PWM profile PWM A Slab drying Slab drying submenu TStart 20 C 10 C 30 C Slab drying start temperature TMax 45 C 20 C 60 C Slab...

Страница 11: ...e in system 2 The room thermostat demands cold the outdoor temperature is indicated 5 2 Display values In order to access the display values from the home screen briefly press the right button 5 3 War...

Страница 12: ...in Minimum temperature heating circuit option 5 4 Con guration In order to access the adjustment values from the home screen press the right button for approx 3 s and enter the user code see page 6 Ts...

Страница 13: ...heating circuit TMax Maximum temperature heating circuit option TMax Maximum temperature heating circuit tLimit Time for which the calculated set flow temperature is to be used Remote control Remote c...

Страница 14: ...ing tPLAY Mixer control time for change of flow direction Block prot Blocking protection option PWM PWM profile selection Chiller on Cooling demand on if the dew point switch detects condensation only...

Страница 15: ...on and function en Slab drying Slab drying submenu TStart Start temperature TMax Holding temperature Rise Rise value Rise time Rise duration tBacking TMax holding time Start Activation Deactivation of...

Страница 16: ...nsor Min press Max press Minimum and maximum pressure The balance values can be set back to zero In order to reset a value proceed as follows Select the desired value and press the right button Does t...

Страница 17: ...tomatic operation Off Relay off Man 2 3 Manual mode of the mixer For control and service work the operating mode of the mixer can be manually adjusted Mixer open Relay 2 on Relay 3 off Auto Relays 2 a...

Страница 18: ...plication example 6 1 2 8 9 10 11 12 13 4 5 1 Outdoor temperature sensor 2 Heating circuit flow 3 Return sensor optional 4 Room thermostat 5 Dew point switch optional 6 Boiler demand when voltage 30V...

Страница 19: ...1290 15 1058 80 1309 20 1078 85 1328 25 1097 90 1347 30 1117 95 1366 35 1136 100 1385 40 1155 105 1404 45 1175 110 1423 50 1194 115 1442 Short circuit or line break Disconnected temperature sensors ca...

Страница 20: ...Distributed by Distributed by Caleffi S p A S R 229 no 25 IT 28010 Fontaneto d Agogna NO All contents of this document are protected by copyright...

Отзывы: