background image

6

Installation

Indications,

 functions and options

Operation and function

en

Connect the RPS Grundfos Direct Sensor™  (pressure sensor) to the input S6.
S7 can be used as an input for a potential-free switch for the cooling mode
Pins 2 and 3 come with a pluggable cable link already connected.  If the contact is 
closed (cable link connected), the heating mode will be active when demanded. If 
the contact is open (cable link not connected) and the cooling option is activated, 
the cooling mode will be active when demanded. 
In order to connect a switch, cut the cable link and connect the switch to both 
wires.
The terminal marked PWM A is the control output for a high-effi ciency pump.
If the Central Outdoor Sensor is to be used, connect it to the terminals marked 
VBus with either polarity.

V

Bus

V

Bus

TA

S3

RT

A1

2

S5

TS10

GND

Sensors

S2

S1

100 ... 240 V

T4A

50-60 Hz

N

R3

R2

R1

L

R1-R3|1 (1) A 240 V~

R4|1 (1) A 30V

IP 20

R4

PWM

 

A

R4

Manufactured
by RESOL - TYPE SLT
Heiskampstr. 10
D-45527 Hattingen

S6

S7

161010

AX

AX

The mains connection is at the terminals:
Neutral conductor N
Conductor L
Protective conductor 

 

Î

Use a cable with a cross section of at least 0.75 mm² of the H05VV-F type for 
connecting the device to the mains.

Note:
The connection depends on the system layout selected (see page 7).

The auxiliary terminals can be used instead of R4 as the mixer switch for the heat 
generator, if a voltage higher than 30 V is applied. 
Antifreeze: Standard function – if the temperature at S2 falls below 7 °C , the con-
troller activates the pump for 30 min, in order to reach 20 °C.
Outdoor sensor: If the outdoor temperature sensor is defective, 0 °C is used as 
the reference value.

3   Operation and function

3.1  Buttons and adjustment dial

The controller is operated via 2 buttons and 1 adjustment dial (Lightwheel

®

) below 

the display:
Left button (

)  -  escape button for changing into the previous menu

Right button (

)  -  confi rming / selecting

Lightwheel

®

 

-  scrolling upwards / scrolling downwards, increasing adjustment 

values / reducing adjustment values

3.2   Adjustment values and user code

Adjustment values will only be available if the correct user code has been entered. 
In order to access the user code enquiry from the home screen, press the right 
button (

) for approx. 3 s.

User code: 0322
If the user code has been entered, the adjustment values menu will be displayed.
In order to get back to the home screen, press the left button (

).

If no button is pressed for 5 min, the controller will display the home screen.

Note:
The user code has to be entered again each time you wish to access the 
adjustment values menu.

Содержание 161010

Страница 1: ...nce from this unit Please keep this manual safe Manual en Heating controller Manual for the specialised craftsman Installation Operation Troubleshooting Digital controller with system representation 1...

Страница 2: ...tem are not exposed to strong electromagnetic fields Subject to technical change Errors excepted Target group These instructions are exclusively addressed to authorised skilled personnel Only qualifie...

Страница 3: ...allation 5 2 1 Mounting 5 2 2 Electrical connection 5 3 Operation and function 6 3 1 Buttons and adjustment dial 6 3 2 Adjustment values and user code 6 3 3 Control LED 7 4 Systems 7 5 Indications fun...

Страница 4: ...acity 4 A 240V Power supply 100 240V 50 60 Hz Supply connection typeY attachment Power consumption 1 W Mode of operation type 1 B C Y action Rated impulse voltage 2 5 kV Data interface VBus VBus curre...

Страница 5: ...ning screw 2 2 Electrical connection WARNING Electric shock Upon opening the housing live parts are exposed Always disconnect the device from power supply before opening the housing ATTENTION ESD dama...

Страница 6: ...ng the device to the mains Note The connection depends on the system layout selected see page 7 The auxiliary terminals can be used instead of R4 as the mixer switch for the heat generator if a voltag...

Страница 7: ...ipped with a non adjustable safety shutdown function If the temperature at S2 reaches or exceeds 90 C the mixer closes The warning symbol appears on the screen and the Lightwheel flashes yellow If the...

Страница 8: ...pressure monitoring tMixer 75 s 30 240 s Mixer runtime Corr tMixer 90 s 5 300 s Surplus mixer runtime when the mixer is closing tPLAY 4 s 1 15 s Mixer control time for change of flow direction Block...

Страница 9: ...a switch for remotely controlling the heating cooling mode Contact open cooling mode Contact closed heating mode If the Condensation option is activated the controller monitors a dew point switch If t...

Страница 10: ...lock prot Yes Yes No Blocking protection option PWM Heating Heating Solar PWM profile PWM A Slab drying Slab drying submenu TStart 20 C 10 C 30 C Slab drying start temperature TMax 45 C 20 C 60 C Slab...

Страница 11: ...e in system 2 The room thermostat demands cold the outdoor temperature is indicated 5 2 Display values In order to access the display values from the home screen briefly press the right button 5 3 War...

Страница 12: ...in Minimum temperature heating circuit option 5 4 Con guration In order to access the adjustment values from the home screen press the right button for approx 3 s and enter the user code see page 6 Ts...

Страница 13: ...heating circuit TMax Maximum temperature heating circuit option TMax Maximum temperature heating circuit tLimit Time for which the calculated set flow temperature is to be used Remote control Remote c...

Страница 14: ...ing tPLAY Mixer control time for change of flow direction Block prot Blocking protection option PWM PWM profile selection Chiller on Cooling demand on if the dew point switch detects condensation only...

Страница 15: ...on and function en Slab drying Slab drying submenu TStart Start temperature TMax Holding temperature Rise Rise value Rise time Rise duration tBacking TMax holding time Start Activation Deactivation of...

Страница 16: ...nsor Min press Max press Minimum and maximum pressure The balance values can be set back to zero In order to reset a value proceed as follows Select the desired value and press the right button Does t...

Страница 17: ...tomatic operation Off Relay off Man 2 3 Manual mode of the mixer For control and service work the operating mode of the mixer can be manually adjusted Mixer open Relay 2 on Relay 3 off Auto Relays 2 a...

Страница 18: ...plication example 6 1 2 8 9 10 11 12 13 4 5 1 Outdoor temperature sensor 2 Heating circuit flow 3 Return sensor optional 4 Room thermostat 5 Dew point switch optional 6 Boiler demand when voltage 30V...

Страница 19: ...1290 15 1058 80 1309 20 1078 85 1328 25 1097 90 1347 30 1117 95 1366 35 1136 100 1385 40 1155 105 1404 45 1175 110 1423 50 1194 115 1442 Short circuit or line break Disconnected temperature sensors ca...

Страница 20: ...Distributed by Distributed by Caleffi S p A S R 229 no 25 IT 28010 Fontaneto d Agogna NO All contents of this document are protected by copyright...

Отзывы: