background image

7

Installation

Indications,

 functions and options

Operation and function

en

3.3    Control LED

The controller is equipped with a multicolour LED in the centre of the  Lightwheel

®

indicating the following states:

Colour

Permanently shown

Flashing

Green 

Everything OK

Manual mode: at least one relay in manual 
mode (OffMax or Min)

Yellow

PMin has fallen below the threshold, TMax 
exceeded by up to 5 K überschritten

Red

Sensor fault, safety shutdown active, TMax 
exceeded by > 5 K 

4   Systems

System 1 (fl ow temperature controlled heating with optional effi ciency 
control of the heat exchange 
 –  fl ow controlled cooling)

Flow

Return

R2 = open
R3 = closed

R1

S3 (optional)

S2

The controller monitors the room thermostat (TA).

If the room thermostat demands heat, the pump (R1) starts and R4 is energised for 
the heating demand. The temperature at S2 is monitored. The mixer is controlled so 
that the adjusted temperature Tset is reached and maintained at S2.
If the TFcalculated option (return temperature monitoring S3, factory setting = 
active) is activated, the controller runs a heat demand-based calculation of the set 
fl ow temperature needed for keeping the system at the optimum temperature. For 
this  purpose,  the  return  temperature  (S3)  is  monitored. The  calculated  set  fl ow 
temperature is displayed as TFset..
The controller is equipped with a non-adjustable safety shutdown function. If the 
temperature at S2 reaches or exceeds 90 °C, the mixer closes. The warning symbol 

 appears on the screen and the Lightwheel

®

 fl ashes yellow. If the temperature 

at S2 reaches or exceeds 95 °C,R1 and R4 switch off. The Lightwheel

®

 fl ashes red.

If the TMax option is activated, the value for the safety shutown function can be 
reduced. If the temperature at S2 exceeds TMax by less than 5 K, the warning sym-
bol 

 appears on the screen and the Lightwheel

®

 fl ashes yellow. If the temperature 

at S2 exceeds TMax  by  more  than  5  K,  R1  and  R4  switch  off. The  Lightwheel

®

 

fl ashes red.
If the Cooling  option  is  activated,  the  mixer  is  controlled  so  that  the  adjusted 
cooling temperature TCool is reached and maintained at S2. The S7 contact can be 
used for connecting a switch for remotely controlling the heating / cooling mode. 
Contact open = cooling mode
Contact closed = heating mode
If the Condensation  option  is  activated,  the  controller  monitors  a  dew  point 
switch.  If  the  dew  point  switch  triggers  an  alarm,  cooling  stops  and  the  warning 
symbol is indicated. If the humidity falls again below the adjusted value, the cooling 
mode continues.

Terminal allocation
S1 

=  outdoor temperature sensor

S2 

=  heating circuit fl ow

S3/RTA12  =  return sensor (optional)
TA 

=  room thermostat

S5/TS10  =  dew point switch (optional)
S6 

=  RPS Grundfos Direct Sensor™ pressure sensor (optional)

S7 

=  contact for remotely controlling the heating / cooling mode (optional)

R1 

= pump

R2 

=  mixer open

R3 

=  mixer closed

Содержание 161010

Страница 1: ...nce from this unit Please keep this manual safe Manual en Heating controller Manual for the specialised craftsman Installation Operation Troubleshooting Digital controller with system representation 1...

Страница 2: ...tem are not exposed to strong electromagnetic fields Subject to technical change Errors excepted Target group These instructions are exclusively addressed to authorised skilled personnel Only qualifie...

Страница 3: ...allation 5 2 1 Mounting 5 2 2 Electrical connection 5 3 Operation and function 6 3 1 Buttons and adjustment dial 6 3 2 Adjustment values and user code 6 3 3 Control LED 7 4 Systems 7 5 Indications fun...

Страница 4: ...acity 4 A 240V Power supply 100 240V 50 60 Hz Supply connection typeY attachment Power consumption 1 W Mode of operation type 1 B C Y action Rated impulse voltage 2 5 kV Data interface VBus VBus curre...

Страница 5: ...ning screw 2 2 Electrical connection WARNING Electric shock Upon opening the housing live parts are exposed Always disconnect the device from power supply before opening the housing ATTENTION ESD dama...

Страница 6: ...ng the device to the mains Note The connection depends on the system layout selected see page 7 The auxiliary terminals can be used instead of R4 as the mixer switch for the heat generator if a voltag...

Страница 7: ...ipped with a non adjustable safety shutdown function If the temperature at S2 reaches or exceeds 90 C the mixer closes The warning symbol appears on the screen and the Lightwheel flashes yellow If the...

Страница 8: ...pressure monitoring tMixer 75 s 30 240 s Mixer runtime Corr tMixer 90 s 5 300 s Surplus mixer runtime when the mixer is closing tPLAY 4 s 1 15 s Mixer control time for change of flow direction Block...

Страница 9: ...a switch for remotely controlling the heating cooling mode Contact open cooling mode Contact closed heating mode If the Condensation option is activated the controller monitors a dew point switch If t...

Страница 10: ...lock prot Yes Yes No Blocking protection option PWM Heating Heating Solar PWM profile PWM A Slab drying Slab drying submenu TStart 20 C 10 C 30 C Slab drying start temperature TMax 45 C 20 C 60 C Slab...

Страница 11: ...e in system 2 The room thermostat demands cold the outdoor temperature is indicated 5 2 Display values In order to access the display values from the home screen briefly press the right button 5 3 War...

Страница 12: ...in Minimum temperature heating circuit option 5 4 Con guration In order to access the adjustment values from the home screen press the right button for approx 3 s and enter the user code see page 6 Ts...

Страница 13: ...heating circuit TMax Maximum temperature heating circuit option TMax Maximum temperature heating circuit tLimit Time for which the calculated set flow temperature is to be used Remote control Remote c...

Страница 14: ...ing tPLAY Mixer control time for change of flow direction Block prot Blocking protection option PWM PWM profile selection Chiller on Cooling demand on if the dew point switch detects condensation only...

Страница 15: ...on and function en Slab drying Slab drying submenu TStart Start temperature TMax Holding temperature Rise Rise value Rise time Rise duration tBacking TMax holding time Start Activation Deactivation of...

Страница 16: ...nsor Min press Max press Minimum and maximum pressure The balance values can be set back to zero In order to reset a value proceed as follows Select the desired value and press the right button Does t...

Страница 17: ...tomatic operation Off Relay off Man 2 3 Manual mode of the mixer For control and service work the operating mode of the mixer can be manually adjusted Mixer open Relay 2 on Relay 3 off Auto Relays 2 a...

Страница 18: ...plication example 6 1 2 8 9 10 11 12 13 4 5 1 Outdoor temperature sensor 2 Heating circuit flow 3 Return sensor optional 4 Room thermostat 5 Dew point switch optional 6 Boiler demand when voltage 30V...

Страница 19: ...1290 15 1058 80 1309 20 1078 85 1328 25 1097 90 1347 30 1117 95 1366 35 1136 100 1385 40 1155 105 1404 45 1175 110 1423 50 1194 115 1442 Short circuit or line break Disconnected temperature sensors ca...

Страница 20: ...Distributed by Distributed by Caleffi S p A S R 229 no 25 IT 28010 Fontaneto d Agogna NO All contents of this document are protected by copyright...

Отзывы: