4.1.10 System cooling 

CMX:  
Maximum collector temp. 
Adjustment range  
210 ... 380 °F 
Factory setting 250 °F

If the adjusted maximum tank temperature is reached, the 
solar system switches-off. If now the collector temperature 
raises to the adjusted maximum collector temperature 
(CMX), the solar pump remains activated until this limit 
temperature value is again underrun. The tank tempe rature 
might continue to raise (subordinated active maximum 
tank temperature), but only until 203 °F (emergency shut-
down of the tank). If the tank tempe rature is higher than 
the maximum tank temperature (S MX) and the collector 
temperature is lower by at least 5 K than the tank tempe-
rature, the solar system remains activated until the tank is 
again cooled down by the collector and the tubes under the 
adjusted maximum temperature (S MX). 
In case of active system cooling on the display is shown   
(flashing). Due to the cooling function the solar system can 
be kept operable for a longer period on hot summer days 
and a thermal release of the collector and the heat transfer 
medium is ensured as well.

OCX:  
Option system cooling 
Adjustment OFF ... ON 
Factory setting ON

4.1.11   Option minimum collector limitation

CMN
Minimum collector tempera-
ture Adjustment range  

 

14 ... 32 °F 
Factory setting 50 °F

OCN:  
Mimimum collector limitation 
Adjustment range OFF / ON 
Factory setting OFF

The minimum collector temperature is a minimum switching 
temperature,  which  must  be  exceeded  so  that  the  solar 
pump (R1/R2) is switched-on. The minimum temperature 
shall avoid a steady starting-up of the solar pump (or solid 
fuel boiler charging pumps) for low collector temperatures. 
If the minimum temperature is underrun, in the display is 
shown   (flashing).

4.1.13 Recooling function

4.1.12   Option antifreeze function

CFR
Antifreeze temperature 
Adjustment range  

 

14 ... 50 °F 
Factory setting 40 °F

OCF:  
Antifreeze function 
Adjustment range  

 

OFF / ON 
Factory setting OFF

The antifreeze function activates the loading circuit bet-
ween collector and tank if the adjusted antifreeze function 
is underrun in order to protect the medium that it will not 
freeze or „get thick“. If the adjusted antifreeze temperature 
is exceeded by 2 °F, the loading circuit will be deactivated.
Please note:
As there is only a limited heat quantity of the tank available 
for this function, the antifreeze function should only be used 
in regions with few days of temperatures around freezing 
point.

If  the  adjusted  maximum  tank  temperature  (S  MX
is reached, the solar pump remains activated in order 
to  avoid  an  overheating  of  the  collector. The  tank 
temperature might continue to increase but only up to  
203 °F (emergency shutdown of the tank).
In the evening the solar system continues running until 
the tank is cooled down to the adjusted maximum tank 
temperature via collector and pipes.

OREC: 
option recooling 
adjustment range 
OFF ... ON 

 

Factory setting: OFF

Содержание iSolar 3

Страница 1: ...Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Mounting Connection Handling Fault localization Examples manual 49005100 49005100...

Страница 2: ...micro films and the storage into electronic systems Editor CALEFFI NORTH AMERICA Inc Important notice We took a lot of care over the texts and drawings of this manual and to the best of our knowledge...

Страница 3: ...4 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display System screen for sys tems visualisation 16 segment display 7 segment display 8 symbols for system stat...

Страница 4: ...lief supports and screws Depending on the version the controller is equipped with 2 relays to which the consumers e g pumps valves etc can be connected Relay 1 18 conductor R1 17 neutral conductor N 1...

Страница 5: ...nsors and after heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of clamps for system 2 Symbol Specification S1 collector sensor S2 tank sensor below...

Страница 6: ...d for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep...

Страница 7: ...he flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only syste...

Страница 8: ...types of antifreeze Corresponding channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr s...

Страница 9: ...rating hours of the respective relay h P Full hours are shown on the display The operating hours added up can be reset As soon as one operating hours channel is selected the symbol in permanently show...

Страница 10: ...note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe rature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F...

Страница 11: ...OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a...

Страница 12: ...sed for use of surplus energy or an after heating AH O AH F the thermostat function is used for after heating AH O AH F the thermostat function is used for use of surplus energy On the display is show...

Страница 13: ...47 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defectiv...

Страница 14: ...fication no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and T...

Страница 15: ...up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is t...

Страница 16: ...tening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiatio...

Отзывы: