background image

© 07127 isolar3.mon

us.ind

d

| 

10

4.1.7 

 ∆

T-regulation

Type of antifreeze:
0 : water 

 

1 : propylene glycol 

 

2 : ethylene glycol 

 

3 : Tyfocor

®

 LS / G-LS

kWh/MWh:Heat quantity 
in kWh / MWh 
Display channel

MEDT: Type of antifreeze  
Adjustment range 0 ... 3 
Factory setting 1

MED%: Concentration of 
antifreeze in (Vol-) % 

 

MED% is blinded out by 
MEDT 0 and 3. 
Adjustment range 20 ... 70 
Factory setting 45

The heat quantity transported is measured by the indication 
of the volume flow and the reference sensor of feed flow 
S1 and return flow S4. It is shown in kWh-parts in the in-
dication channel kWh and in MWh-parts in the indication 
channel MWh. The sum of both channels form the total 
heat output.
The heat quantity added up can be reset. As soon as one 

of the display channels of the heat quantity is selected, the 
symbol 

 is permanently shown on the display. The button 

SET (3) must be pressed for approx. 2 seconds in order to 

get back into the RESET-mode of the counter. The display-

symbol 

 is flashing and the value for heat quantity will be 

set to 0. In order to finish the RESET-procedure, the button 

 must be pressed for con firmation. 

In order to interrupt the RESET-procedure, no button 

should be pressed for about 5 seconds. The controller re-

turns automatically into indication mode.

Please note: Switch-on temperature difference DO must 
be at least 2 °Ra higher than the switch-off tempe rature-
difference DF.

DT O:  
Switch-on temperature 
Adjustment range  
2,0 ... 40,0 °Ra 
Factory setting 12.0
DT F
Switch-off temperature  diff. 
Adjustment range  
1,0 ... 38 °Ra 
Factory setting 8.0 °Ra

Primarily the controller works in the same way as a standard 
differential  controller.  If  the  switch-on  difference  (DT O
is reached, the pump is activated. If the adjusted switch-off 
temperature is underrun (DT F), the controller switches-
off.

4.1.8 Maximum tank temperature

If the adjusted maximum temperature is exceeded, a further 
loading of the tank is stopped so that a damaging overheating 
can  be  avoided.  If  the  maximum  tank  temperature  is 
exceeded, on the display is shown and  .
Please note: The controller is equipped with a security-
switch-off of the tank, which avoids a further loading of the 
tank if 203 °F are reached at the tank.

S MX:  
Maximum tank temp. 
Adjustment range 
40 ... 205 °F 

 

Factory setting 140 °F

4.1.9 Limit collector temperature  

  Collector emergency shutdown

If the adjusted collector limit temperature (EM) is exceeded, 
the solar pump (R1/R2) is deactivated in order to avoid a 
damaging overheating of the solar components (collector 
emergency  shutdown). The  limit  temperature  is  set  to 
285 °F but it can be changed within the adjustment range of 
230 ... 400 °F. In the display is shown   (flashing).

EM
Limit collector temperature 
Adjustment range 

 

230 ... 400 °F, 
Factory setting 285 °F

Содержание iSolar 3

Страница 1: ...Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Mounting Connection Handling Fault localization Examples manual 49005100 49005100...

Страница 2: ...micro films and the storage into electronic systems Editor CALEFFI NORTH AMERICA Inc Important notice We took a lot of care over the texts and drawings of this manual and to the best of our knowledge...

Страница 3: ...4 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display System screen for sys tems visualisation 16 segment display 7 segment display 8 symbols for system stat...

Страница 4: ...lief supports and screws Depending on the version the controller is equipped with 2 relays to which the consumers e g pumps valves etc can be connected Relay 1 18 conductor R1 17 neutral conductor N 1...

Страница 5: ...nsors and after heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of clamps for system 2 Symbol Specification S1 collector sensor S2 tank sensor below...

Страница 6: ...d for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep...

Страница 7: ...he flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only syste...

Страница 8: ...types of antifreeze Corresponding channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr s...

Страница 9: ...rating hours of the respective relay h P Full hours are shown on the display The operating hours added up can be reset As soon as one operating hours channel is selected the symbol in permanently show...

Страница 10: ...note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe rature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F...

Страница 11: ...OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a...

Страница 12: ...sed for use of surplus energy or an after heating AH O AH F the thermostat function is used for after heating AH O AH F the thermostat function is used for use of surplus energy On the display is show...

Страница 13: ...47 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defectiv...

Страница 14: ...fication no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and T...

Страница 15: ...up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is t...

Страница 16: ...tening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiatio...

Отзывы: