d

| 

4

display

pushbutton

can fuse 4A

cable conduits with strain 
relief

cover

1.1  Mounting

The unit must only be located internally. It is not suitable 
for  installation  in  hazardous  locations  and  should  not  be 
sited near to any electromagnetic field. The controller must 
additionally be equipped with an all-polar gap of at least 3 mm 
or with a gap according to the valid installaton regulations, 
e.g. LS-switches or fuses. Please pay attention to a separate 
laying of the cable lines and installation of ac power supply.
1.  Unscrew  the  cross-recessed  screw  of  the  cover  and 

remove it from the housing.

2.  Mark the upper fastening point on the wall and premount 

the enclosed dowel and screw.

3.  Hang up the housing at the upper fastening point and mark 

the lower fastening point on the underground (hole pitch 
130 mm), afterwards put the lower dowel.

4.  Fasten the housing at the underground.

1.  Installation

Warning!
Switch-off power supply before 
opening the housing.

1.2 Electrical wiring

The power supply to the controller must only be made by 
an external power supply switch (last step of installation!) 
and the line voltage must be 115 Volt (50...60 Hz). Flexible 
lines are to be fixed at the housing by enclosed strain relief 
supports and screws.
Depending on the version the controller is equipped with 

2 relays to which the consumers e.g. pumps, valves etc. 

can be connected:

• Relay 1 

 

18 = conductor R1 

 

17 = neutral conductor N 

 

13 = ground clamp 

• Relay 2  

 

16 = conductor R2 

 

15 = neutral conductor N 

 

14 = ground clamp 

The temperature sensors (S1 up to S4) will be connected 

to the following terminals independently of the polarity:
1 / 2 =  Sensor 1 (e.g. Sensor collector 1)
3 / 4 =  Sensor 2 (e.g. Sensor tank 1)

5 / 6 =  Sensor 3 (e.g. Sensor TSPO)

7 / 8 =  Sensor 4 (e.g. Sensor TRL)

The power supply is effected to the clamps:
19 = neutral conductor N
20 = conductor L
12 = ground clamp 

hanging

fixation

Electrostatic discharge can lead to damages of elec-
tronic components!

Dangerous voltage on contact!

net clamps

fuse

consumer clamps

Sensor clamps

earthing clamps

VBus

®

The controller comes with a VBus

®

 for data communication 

and energy supply of external modules. The connection 

is effected with optional polarity at the clamps marked 

with„VBus

®

“. Via this data Bus you can install one or more 

VBus

®

 modules, e.g.:

• heat quant. measurement module WMZ-M1

• large display GA3

• Data logger, DL1

• Data teleindication, DFA2

Additionaly, the controller can be connected to the PC with 

the help of a RS-COM adapter. With the ServiceCenter 

Software (RCS) the controller parameters can be changed, 

measurements can be read out, processed and visualised. 

The software enables an easy function control and adjust-

ment of the system. 

Содержание iSolar 3

Страница 1: ...Thanks for buying this product Read this manual carefully to get the best perfomance from this unit Mounting Connection Handling Fault localization Examples manual 49005100 49005100...

Страница 2: ...micro films and the storage into electronic systems Editor CALEFFI NORTH AMERICA Inc Important notice We took a lot of care over the texts and drawings of this manual and to the best of our knowledge...

Страница 3: ...4 F Size 172 x 110 x 46 mm Mounting wall mounting mounting into patch panels is possible Display System screen for sys tems visualisation 16 segment display 7 segment display 8 symbols for system stat...

Страница 4: ...lief supports and screws Depending on the version the controller is equipped with 2 relays to which the consumers e g pumps valves etc can be connected Relay 1 18 conductor R1 17 neutral conductor N 1...

Страница 5: ...nsors and after heating The sensor S4 TRF can optionally be used for heat quantity balancing Arr 2 1 2 2 Allocation of clamps for system 2 Symbol Specification S1 collector sensor S2 tank sensor below...

Страница 6: ...d for scrolling forward through the indication menu or to increase the adjustment values The backwards key 2 is accordingly used for the reverse function For adjustment of last indication channel keep...

Страница 7: ...he flow direction or the current bre aking capacity are always shown Heating circuit Tank 1 and 2 with heat exchanger After heating with burner symbol Temperature sensor 2 2 3 System screen only syste...

Страница 8: ...types of antifreeze Corresponding channel is only available if the option heat quantity measurement is deactivated OWMZ Please note S3 and S4 are only indicated if sensors are connected channel Arr s...

Страница 9: ...rating hours of the respective relay h P Full hours are shown on the display The operating hours added up can be reset As soon as one operating hours channel is selected the symbol in permanently show...

Страница 10: ...note Switch on temperature difference DO must be at least 2 Ra higher than the switch off tempe rature difference DF DT O Switch on temperature Adjustment range 2 0 40 0 Ra Factory setting 12 0 DT F...

Страница 11: ...OFF ON Factory setting OFF The minimum collector temperature is a minimum switching temperature which must be exceeded so that the solar pump R1 R2 is switched on The minimum temperature shall avoid a...

Страница 12: ...sed for use of surplus energy or an after heating AH O AH F the thermostat function is used for after heating AH O AH F the thermostat function is used for use of surplus energy On the display is show...

Страница 13: ...47 86 1117 203 1366 95 1136 212 1385 104 1155 221 1404 113 1175 230 1423 122 1194 239 1442 Resistance values of the Pt1000 sensors Check the power supply o k The can fuse of the controller is defectiv...

Страница 14: ...fication no Heat exchanger plugged yes no Cleaning Heat exchanger too small yes New calculation of the dimension no Plausibility control of the option tube collector spe cial function Change Ton and T...

Страница 15: ...up in manual operation yes There is no current check fuses replace them and check power supply The adjusted tempe rature difference for starting the pump is too high choose a matching setting no Is t...

Страница 16: ...tening Sensors Our product range includes high precision platin temperatu re sensors flatscrew sensors ambient temperature sensors indoor temperature sensors cylindrical clip on sensors and irradiatio...

Отзывы: