© 07127 isolar3.mon
us.ind
d
|
4
display
pushbutton
can fuse 4A
cable conduits with strain
relief
cover
1.1 Mounting
The unit must only be located internally. It is not suitable
for installation in hazardous locations and should not be
sited near to any electromagnetic field. The controller must
additionally be equipped with an all-polar gap of at least 3 mm
or with a gap according to the valid installaton regulations,
e.g. LS-switches or fuses. Please pay attention to a separate
laying of the cable lines and installation of ac power supply.
1. Unscrew the cross-recessed screw of the cover and
remove it from the housing.
2. Mark the upper fastening point on the wall and premount
the enclosed dowel and screw.
3. Hang up the housing at the upper fastening point and mark
the lower fastening point on the underground (hole pitch
130 mm), afterwards put the lower dowel.
4. Fasten the housing at the underground.
1. Installation
Warning!
Switch-off power supply before
opening the housing.
1.2 Electrical wiring
The power supply to the controller must only be made by
an external power supply switch (last step of installation!)
and the line voltage must be 115 Volt (50...60 Hz). Flexible
lines are to be fixed at the housing by enclosed strain relief
supports and screws.
Depending on the version the controller is equipped with
2 relays to which the consumers e.g. pumps, valves etc.
can be connected:
• Relay 1
18 = conductor R1
17 = neutral conductor N
13 = ground clamp
• Relay 2
16 = conductor R2
15 = neutral conductor N
14 = ground clamp
The temperature sensors (S1 up to S4) will be connected
to the following terminals independently of the polarity:
1 / 2 = Sensor 1 (e.g. Sensor collector 1)
3 / 4 = Sensor 2 (e.g. Sensor tank 1)
5 / 6 = Sensor 3 (e.g. Sensor TSPO)
7 / 8 = Sensor 4 (e.g. Sensor TRL)
The power supply is effected to the clamps:
19 = neutral conductor N
20 = conductor L
12 = ground clamp
hanging
fixation
Electrostatic discharge can lead to damages of elec-
tronic components!
Dangerous voltage on contact!
net clamps
fuse
consumer clamps
Sensor clamps
earthing clamps
VBus
®
The controller comes with a VBus
®
for data communication
and energy supply of external modules. The connection
is effected with optional polarity at the clamps marked
with„VBus
®
“. Via this data Bus you can install one or more
VBus
®
modules, e.g.:
• heat quant. measurement module WMZ-M1
• large display GA3
• Data logger, DL1
• Data teleindication, DFA2
Additionaly, the controller can be connected to the PC with
the help of a RS-COM adapter. With the ServiceCenter
Software (RCS) the controller parameters can be changed,
measurements can be read out, processed and visualised.
The software enables an easy function control and adjust-
ment of the system.