U
ser
'
s
G
Uide
— 47
(cont’d)
STaRTER SIZE
What NEMA size Starter is required for a 575 Volt, 3Ø, 20 HP
Induction motor?
KeysTRoKe
DIsPlay
0.
1. Set to 3-phase:
(3Ø)
3Ø
3 Ph
2. Enter Volts:
VolT 575.
3. Enter HP:
InD* 20. hP
*
If
iND
is not shown, press
until
iND
is displayed in the upper left
area of the display.
4. Solve for Starter Size:
(Starter)
sTaR
sIZe
2
OVERlOaD PROTECTION SIZE
What Overload Protection device size is required for an Induction
motor with a nameplate Current rating of 19.2 Amps and a 1.0
service factor? What is the required Overload rating at 125% (for a
1.15 service factor)?
KeysTRoKe
DIsPlay
0.
1. Enter nameplate Current:
aMPs 19.2
2. Find Overload size:
aMPs 22.08 o l
3. Display percent used:
%flC 115.
%