ambient temperature (amb°) —
Permanently
enters ambient temperature for determining
ampacity-derived Wire Sizes. Ambient temperature
will only change when entering a new value or by
resetting the calculator. Defaults to 30°C (86°F).
amb
will display when the Ambient Temperature is
other than 30°C (86°F).
Note:
The temperature units can be displayed in
Celsius (°C) or Fahrenheit (°F) by changing the
Preference Setting (see
Preference settings
section).
copper/aluminum (cu/al) —
Used to toggle
between Copper (default) and Aluminum
Wire Types. When the Wire Type is revised,
any calculated Wire Size will be re-calculated
automatically. If a Wire Size is entered with the
wrong Wire Type, pressing
will change
the material type without changing the size.
Free air (Frair) —
Sets calculator to Free Air
mode, which refers to NEC Table 310.15(B)(17)
for Wire Size calculations.
60°c Wire insulation —
Sets calculator to 60°C
Wire Insulation Type for Wire Size calculations.
This is the default setting.
75°c Wire insulation —
Sets calculator to 75°C
Wire Insulation Type for Wire Size calculations.
90°c Wire insulation —
Sets calculator to 90°C
Wire Insulation Type for Wire Size calculations.