FLAME WITH NO CALL FOR HEAT (FLAME FAULT)
•
If at any time the main valve fails to close completely and maintains a flame, the full time flame
sense circuit will detect it and energize the combustion blower. Should the main valve later close off
completely removing the flame signal, the combustion blower will power off.
IGNITION LOCK OUT (FAILURE TO LIGHT)
•
FENWAL DSI Module will attempt three ignition trials before going into lockout. The valve relay will
be de-energized immediately, and the combustion blower will be turned off.
•
Recovery from lockout requires a manual reset by either resetting the thermostat or removing 24
volts, or removing the electrical power supply for a period of 5-seconds.
•
If the thermostat is still calling for heat after one hour, the control will automatically reset and
attempt to ignite the burner again.
If unit still does not operate, proceed as follows:
•
Check flame sensor current. (see below)
•
Check electrode for cracks and proper location, (see page 80)
FLAME SENSOR CURRENT CHECK
SERVICE CHECKS
Flame current is the current which
passes through the flame from the
sensor to the ground. The minimum
flame current necessary to keep the
system from lockout is .7 micro amps.
To measure flame current, connect
an analog DC micro ammeter to the
FC- FC terminals per figure. Meter
should read. 7 uA or higher. If meter
reads below "0" on scale, meter leads
are reversed. Disconnect power and
reconnect meter leads for proper
polarity.
Figure 64. FLAME SENSOR CURRENT CHECK
Содержание SR Series
Страница 17: ...SR SERIES 13 8 0 PACKAGING CONTENTS DESCRIPTION OF PARTS BURNER PACKAGE Figure 10 BURNER PACKAGE CONTENTS...
Страница 18: ...SR SERIES 14 PIPE BOXES Figure 11 PIPE BOX CONTENT...
Страница 19: ...SR SERIES 15 10 3 M REFLECTOR PACKAGE Figure 12 10 3 M REFLECTOR PACKAGE CONTENTS...
Страница 20: ...SR SERIES 16 15 4 16 M REFLECTOR PACKAGE Figure 13 15 4 16 M REFLECTOR PACKAGE CONTENTS...
Страница 21: ...SR SERIES 17 20 6 1 M REFLECTOR PACKAGE Figure 14 20 6 1 M REFLECTOR PACKAGE CONTENTS...
Страница 22: ...SR SERIES 18 30 9 1 M REFLECTOR PACKAGE Figure 15 30 9 1 M REFLECTOR PACKAGE CONTENTS...
Страница 23: ...SR SERIES 19 40 12 2 M REFLECTOR PACKAGE Figure 16 40 12 2 M REFLECTOR PACKAGE CONTENTS...
Страница 24: ...SR SERIES 20 50 15 2 M REFLECTOR PACKAGE Figure 17 50 15 2 M REFLECTOR PACKAGE CONTENTS...
Страница 25: ...SR SERIES 21 60 18 3 M REFLECTOR PACKAGE Figure 18 60 18 3 M REFLECTOR PACKAGE CONTENTS...
Страница 26: ...SR SERIES 22 70 21 3 M REFLECTOR PACKAGE Figure 19 70 21 3 M REFLECTOR PACKAGE CONTENTS...
Страница 27: ...SR SERIES 23 80 24 4 M REFLECTOR PACKAGE Figure 20 80 24 4 M REFLECTOR PACKAGE CONTENTS...
Страница 28: ...SR SERIES 24 10 3 M EXTENSION KIT Figure 21 10 3 M EXTENSION PACKAGE CONTENTS...
Страница 29: ...SR SERIES 25 SIDE REFLECTOR PACKAGE Figure 22 SIDE REFLECTOR PACKAGE CONTENTS...
Страница 30: ...SR SERIES 26 90 ELBOW PACKAGE Figure 23 90 ELBOW PACKAGE 180 U BEND PACKAGE Figure 24 180 U BEND PACKAGE...
Страница 34: ...SR SERIES 30 HORIZONTAL INSTALLATION 10 3 M REFLECTOR PACKAGE Figure 28 HORIZONTAL INSTALLATION 10 3 M PACKAGE...
Страница 56: ...SR SERIES 52 SIDE REFLECTOR Figure 52 SIDE REFLECTOR INSTALLATION...
Страница 62: ...SR SERIES 58 ROOF EXHAUST Single Unit Use B style chimney SINGLE UNIT INTO ONE 1 B Vent Chimney...
Страница 78: ...SR SERIES 74 24 0 GAS VALVES Figure 62 GAS VALVE Figure 63 PRESSURE REGULATOR...
Страница 94: ...SR SERIES 90...
Страница 95: ...SR SERIES 91...