SATURNO
10
Fig. 9 - DIRECTLY FROM OUTSIDE
Fig. 10 - INDIRECTLY FROM THE ADJACENT ROOM
LEGEND
Fig. 10
A
AIR INLET
B
ROOM TO BE VENTILATED
C
INCREASE OF THE GAP UNDER THE DOOR
Fig. 11 - Air inlet for sealed-chamber installation
DISTANCE (metres)
The air inlet must be at a distance of:
1,5 m
BELOW
Doors, windows, smoke outlets, gaps, ....
1,5 m
HORIZONTALLY
Doors, windows, smoke outlets, gaps, ....
0,3 m
ABOVE
Doors, windows, smoke outlets, gaps, ....
1,5 m
AT A DISTANCE
from smoke outlet
It is possible to connect the air required for combustion directly to the outside air inlet, with a pipe of at least Ø50mm, with maxi-
mum length of 3 linear metres; each pipe bend shall be considered equivalent to a linear metre. To attach the pipe see the rear of the
stove. For stoves installed in studio flats, bedrooms and bathrooms (where allowed), it is mandatory to connect the combustion air
outside. Specifically for sealed stoves the connection must be sealed in order not to compromise the overall sealing of the system.