LED indicators
Liquid crystal display
Provides detailed info on the status of the fire alarm system, see pages 8 - 11
(General) Fire
Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart this indicator
flashing until it is silenced again
Fire Zones
One or more of these indicators will flash red in an alarm condition to show
which (1-16 or 1-32) zone(s) the fire is in and will go steady when silenced
Supply Present
Normally lit green to show that all of the panel’s power supplies are
functioning correctly
Test
Lit yellow when the panel is in walk test mode. This indicator does NOT light
for any other test condition
Accessed
Lit yellow when the panel is in access level 2 or 3
General Disablement
Lit yellow when one or more zone, sounder, output or relay is disabled
Phased Evacuation
Flashes yellow when there is a phased evacuation in process
General Fault
Flashes yellow when there is a fault condition on the panel. Will always be lit
in conjunction with at least one other fault indicator
Power Supply Fault
Lit yellow when the panel’s power supply or Mains has failed or the panel’s
standby battery is in poor condition
System Fault
Lit yellow when a system error, such as a microprocessor fault, occurs AND
REMAINS LIT EVEN IF THE SYSTEM FAULT CLEARS. THIS SYSTEM FAULT LED CAN
ONLY BE CLEARED BY PRESSING THE CONTROL PANEL RESET BUTTON AT AL2/3.
Sounder Status
Flashes yellow if there is a faulty sounder or a sounder disablement anywhere
on the system
Delays Running
Lit yellow when one or more output delays have been programmed by an engineer.
Flashes yellow when one or more output delays are running.
Button controls
More Information
Displays additional information on any fire or fault conditions that appear
on the panel’s display
(Scroll Up)
5
(1)
Dependent on the status of the panel, these two buttons:
(Scroll Down)
6
(3)
• scroll vertically through any fire or fault conditions that appear on the
panel’s
display
• scroll vertically through the panel’s user menus
• manipulate date, time and disablement settings, etc.
• select Yes/No in the panel’s menu options
• serve as code input buttons to access levels 2 or 3
Accept
4
(2)
Dependent on the status of the panel, these two buttons:
Escape
3
(4)
• scroll horizontally through the panel’s user menus
• escape or accept options available in the panel’s user menus
• serve as code input buttons to access levels 2 or 3
Menu
Provides access to the panel’s user menus
Silence Internal Sounder Silences the panel’s internal sounder
Control Panel Reset
Resets the panel when the sounders are silenced (access levels 2 & 3 only)
Silence / Resound Sounders Silences or resounds the system’s sounders (access levels 2 & 3 only)
Investigate
Starts the panel’s investigate timer function (access levels 2 & 3 only). Only
available if the panel’s investigate function has been enabled by an engineer
Keyswitch control
Turning the keyswitch to the armed position ‘I’ gives the user instant access to
access level 2 (authorised user level). The key is non-removable in position ‘I’.
USER MANUAL & LOG BOOK • Approved Document No. DFU5020000 Rev 3 • Page 7 of 24