
USER MANUAL & LOG BOOK • Approved Document No. DFU5020000 Rev 3 • Page 21 of 24
CAST XFP 16 & 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
FIRE ALARM LOG BOOK
It is recommended that this log book be maintained by a responsible person, who should ensure that every entry
is properly recorded. In the UK, this is necessary to satisfy the recommendations of BS5839-1, compliance with
which may be a requirement of legislation. If your premises are certificated under the Fire Precautions Act, failure
to keep a suitable log book may be a breach of the requirements of the certificate, which is a criminal offence. In
order to satisfy the requirements of BS5839-1 the following must be recorded:
•
The name of the responsible person
•
Brief details of the maintenance arrangements
•
Dates and times of all tests, including fire drills
•
Dates and times of all fires to which the system responds
•
Dates and times of all false alarms
•
Causes, circumstances surrounding and category of false alarms (if known)
•
The identity of any manual call point or fire detector that triggers any of the above fire alarm signals (if known)
•
Dates, times and type of all faults and defects
•
Dates and times of all maintenance, e.g. service visit, or non-routine attention
USER:
SITE ADDRESS:
RESPONSIBLE PERSON(S) ON SITE:
THE SYSTEM WAS DESIGNED BY:
THE SYSTEM WAS INSTALLED BY:
THE SYSTEM WAS COMMISSIONED BY:
THE SYSTEM WAS ACCEPTED BY:
VERIFICATION WAS UNDERTAKEN BY:
THE SYSTEM IS MAINTAINED UNDER CONTRACT BY:
Company:
Address:
Contact No: Expiry Date:
NORMAL HOURS (MON-FRI) TEL:
OUTSIDE NORMAL HOURS TEL:
MANNED CENTRE TEL:
MANNED CENTRE CODE:
THE NORMAL MAXIMUM ATTENDANCE TIME FOR A MAINTENANCE TECHNICIAN IS:
EXPENDABLE COMPONENT REPLACEMENT PERIODS (LIST):
FOR SERVICE (DETAILS OF WHO YOU SHOULD CONTACT IF MAINTENANCE IS REQUIRED)