ACCESS LEVEL 2 (Authorised User) CONTROLS & MENU OPTIONS

Access level 2 is available to authorised, trained personnel only. At this level, the panel’s Silence/
Resound Sounders, Control Panel Reset and Investigate buttons become active and you can:
•  Scroll through any fire or fault conditions that are displayed on the panel’s display
•  View any disablements, or zones that are being tested
•  Enable or disable zones, sounders, outputs, relays and devices
•  Display and/or reset the panel’s event history
•  Set the time and date
•  Change the entry code to access level 2 from its factory default.

Details of how to use the panel’s Silence/Resound Sounders, Control Panel Reset and Investigate 
buttons can be found below.

Entering access level 2 - Using the pushbuttons on the panel

Entry to access level 2 requires the input of a special four digit code.
Press the Menu button on the panel’s front at access level 1. When the ENTER ACCESS LEVEL 2? prompt 
appears, press the Accept

button and you will be asked to enter the code:

Enter the access level 2 code using the 

5

(1), 

4

(2), 

6

(3), 

3

(4) buttons as appropriate. The default code 

to access level 2 is 

3 3 3 3

 (four presses of the 

button). If this does not work, the code may have 

been changed by an authorised user/engineer. A record of any changes should appear on the System 
Set-Up Data Chart on page 20 of this user manual. If they do not, contact your maintenance company.

Entering access level 2 - Using the keyswitch on the panel

Entry to access level 2 is gained by turning the panel’s keyswitch to the armed position ‘I’.

Silencing the alarm sounders

To silence any active alarm sounders, enter access level 2 (see above) and press the Silence/Resound 
Sounders button. The alarm sounders will cease to sound and the panel’s general Fire and relevant 
Fire Zone indicators will go steady.
Should a fire condition occur on another zone whilst the alarm sounders are silenced, the panel:
•  Will activate the sounders programmed by an engineer for activation by the new zone(s) in alarm
•  Will flash the general Fire and appropriate Zone indicator(s) for any new zone(s) in alarm
•  May, if programmed by an engineer, automatically reactivate the silenced alarm sounders and   
  flash any related Fire Zone indicator(s).

Resounding the alarm sounders

Pressing the Silence/Resound Sounders button when the alarm sounders are silenced will resound them. 
Pressing the Silence/Resound Sounders button again will silence the alarm sounders.

Resetting the panel

After the cause of an alarm has been cleared and the alarm sounders have been silenced (see above), 
the panel can be reset by pressing the Control Panel Reset button.
The panel will give a double beep to indicate the reset process has started and, after a few seconds, 
the Fire Zone indicators and general Fire indicator will go out to indicate the process is complete. If 
there are still any fire conditions on any zones, the panel will go back into alarm as before.

Note: The panel’s Investigate button is only active if an engineer has programmed one, 
or more, zones to operate with a 1st-stage investigation delay period (see page 10 for 
detailed information on this feature).

Enter Access Level 2 code:

CAST XFP 16 & 32 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

USER MANUAL & LOG BOOK • Approved Document No. DFU5020000 Rev 3 • Page 14 of 24

Содержание XFP501/CA

Страница 1: ...nalogue Addressable Fire Alarm Control Panel 1 Loop 16 Zone Panel Part No XFP501E CA 1 Loop 32 Zone Panel Part No XFP501 CA 2 Loop 32 Zone Panel Part No XFP502 CA User Manual Log Book Approved Documen...

Страница 2: ...onditions 11 Access level 1 general user controls and menu options 12 13 Displaying fire fault disablement and test events 12 13 Testing the panel s lamps 13 Displaying the panel s alarm counter 13 Ac...

Страница 3: ...e Installation and Programming Manual for this product and have the necessary skills for maintaining the equipment If the panel is damaged in any way expert advice should be sought regarding its repai...

Страница 4: ...e or reset a fire condition to resound the alarm sounders to disable or enable parts of the system to suit prevailing conditions to change the panel s date and time and to test the panel s indicators...

Страница 5: ...faults or false alarms 47h 8 Ensure that any structural or occupancy changes planned for the building are done so with due and early consideration given to any changes that may be required to the fir...

Страница 6: ...em fault delays running supply present more information escape accept EN54 2 EN54 4 XFP The system must be tested regularly If in doubt refer to the user manual CA ST XFP SERIES 176b 10 59 03 24 Jun N...

Страница 7: ...a sounder disablement anywhere on the system Delays Running Lit yellow when one or more output delays have been programmed by an engineer Flashes yellow when one or more output delays are running Butt...

Страница 8: ...uts delayed is displayed if one or more delays to outputs have been programmed by an engineer It indicates that certain outputs which may include sounders relays and or output units will not trigger i...

Страница 9: ...o fire but all previous zones will now appear on a step by step basis with details of which order they went into fire i e 1st zone 2nd zone etc Pressing the More Information button at any time will gi...

Страница 10: ...t up with an investigation delay period Press the More Information button to display the actual device that has triggered the 1st stage fire condition pressing More Information again will count down h...

Страница 11: ...pertinent to that fault will be displayed instead if available For device specific faults pressing the More Information button again will display the unique ID code and address location of the faulty...

Страница 12: ...changes should appear on the System Set Up Data Chart on page 20 of this user manual If they do not contact your maintenance company As soon as the code has been entered correctly you will be taken in...

Страница 13: ...utton once A window similar to the one below will appear Pressing the 5 and 6 buttons will scroll the display through all zones in test mode To return to the main access level 1 menu press the Escape3...

Страница 14: ...I Silencing the alarm sounders To silence any active alarm sounders enter access level 2 see above and press the Silence Resound Sounders button The alarm sounders will cease to sound and the panel s...

Страница 15: ...LIFE AND VOID ITS WARRANTY If you are an engineer details of access level 3 can be found in the panel s separate engineering manual Testing the panel s lamps AL2 3333 Lamp Test This function tests th...

Страница 16: ...and scroll down to the desired function using the 6 button Note The PRINT EVENT HISTORY function is for future AL2 3333 Event Log Functions Display Event History The DISPLAY EVENT HISTORY menu option...

Страница 17: ...cannot be done Instead you must first enable at least one device on the zone using the ENABLE DISABLE DEVICES function before re enabling the zone itself AL2 3333 Set Clear Disablements Enable Disable...

Страница 18: ...flash Next use the 5 and 6 buttons to toggle between enabled and disabled and press the Accept4 button to select the desired option The window will now move to the next device allowing further enablem...

Страница 19: ...nn Alarms Since nn nn nn n AL1 Menu button model dependent MENU NAVIGATION PRESS ACCEPT BUTTON TO MOVE FORWARD PRESS ESCAPE BUTTON TO MOVE BACK PRESS SCROLL BUTTON TO MOVE UP PRESS SCROLL BUTTON TO MO...

Страница 20: ...for access level 2 using the pushbuttons on the panel is 3 3 3 3 four presses of the 6 key If this code is changed make a note of the changes here New access level 2 code Date changed ________________...

Страница 21: ...tests including fire drills Dates and times of all fires to which the system responds Dates and times of all false alarms Causes circumstances surrounding and category of false alarms if known The id...

Страница 22: ...IRE ALARM PANEL Details of tests including fire drills actual fire alarms disablements enablements and faults should be recorded here Note BEFORE ENTERING DETAILS ON THIS FORM PHOTOCOPY ADDITIONAL SHE...

Страница 23: ...ESSABLE FIRE ALARM PANEL PHOTOCOPY ADDITIONAL SHEETS AS REQUIRED DATE TIME EVENT e g test fire alarm signal fault ZONE DEVICE ACTION REQUIRED COMPLETED INITIALS USER MANUAL LOG BOOK Approved Document...

Страница 24: ...NDINGS OF MAINTENANCE TECHNICIAN CATEGORY OF FALSE ALARM FURTHER ACTION REQUIRED DONE PLEASE TICK DATE TIME ZONE WHERE APPLICABLE DEVICE WHERE APPLICABLE REASONS FOR WORK WORK CARRIED OUT FURTHER WORK...

Отзывы: