background image

of the screws and the pump body. The gases are conveyed by the rota-
tion of the screws to the exhaust, where they are discharged.

The COBRA NW screw vacuum pumps are driven by water-cooled
motors.

Oil circuit

Since the complete operating principle works without contact, no oil
circuit is needed in the work area.

Cooling

The vacuum pump is cooled by

a cooling water circuit (4) in the cylinder and motor. This cooling
water circuit is used to cool the motor of the pump, the frequency
inverter and also the body of the NW pump.

NOTE

: The COBRA BC vacuum pumps are always delivered without oil

and without cooling water. Operation without these coolants can result
in damage to the vacuum pump.

Nitrogen system

The nitrogen system performs three main functions

nitrogen is used as dilution gas. It is injected inside the cylinder on
two different places. Nitrogen flow injected in the middle hole is
preset at 2 l/ min and can be adjusted with valve DGR 1, depen-
ding on the application. When flow is too low a warning then an
alarm signal is generated by flowmeter DGF to the PLC. Status of
the pump depends on the alarm function set by user (factory set-
ting : None, pump continues running with an alarm). Dilution im-
proves the screws functioning, especially when sucking corrosive
gases.

nitrogen is used as sealing gas. The nitrogen is injected between
the transmission and the process gas to achieve good closeness.

nitrogen is used as purge gas. The purge eliminates traces of gases
remaining in the vacuum pump. The vacuum pump purge cycle is
programmed in the control and starts, either after a STOP opera-
tion or after an alarm function.
For a correct purge execution, the shut-off valve at the inlet flange
must be closed. The purge cycle lasts about 30 min. (Program-
mable time in the basic parameters).

Optional functions/ Use of available
accessories

A heating jacket attached to the exhaust heats the exhaust up to the li-
mit of 130°C in order to eliminate any condensate.

A handle can be attached to the eyebolt screw in order to facilitate the
handle of the vacuum pump (option)

A pressure receiver mounted at the exhaust , controls the overpressure
at the exhaust. If overpressure is above 0,2 bar, pressure switch gives a
warning signal. If overpressure is above 0,3 bar an alarm is generated.
Status of the pump depends on the alarm function set by user (factory
setting: None, pump continues running with an alarm).

A temperature sensor mounted on the cylinder, measures the tempera-
ture inside the cylinder.

A silencer or sound absorber (optional) at the exhaust reduces the
noise of the pump and collects any condensate.

A leak-protection non-return valve (optional) at the exhaust traps the
condensate in the pump when the pump is switched off.

The LCD controller processes the data of the sensors (see chapter
“Communication with the equipment”) as follows:

discharge pressure

temperature in the cylinder and at the exhaust

current

nitrogen flow rate (dilution, sealing)

cooling water flow rate

speed

frequency

power

The data process with the C.M.S. (Central Monitoring System) (acces-
sory) has the same function as the LCD controller (see operating ins-
tructions of Central Monitoring System).

On/ Off switch

The vacuum pump is delivered with on/ off switch.

Versions

Further vacuum pump descriptions state the nominal displacement and
the design level.

Example: BC 0200 F
BC = standard version
0200 = 165 m

3

/h (80 Hz)

F = Design

Safety

Intended use

DEFINITION

: To rule out any misunderstanding, the term “handling”

of the vacuum pump covers transport, storage, installation and opera-
tion of the pump as well as effects on operating states and troublesho-
oting on the vacuum pump.

The vacuum pump is intended for industrial use. It may only be opera-
ted by qualified personnel.

The different application possibilities and limit values for operation des-
cribed in “Product description” and “Installation requirements” must
be observed by the manufacturer of the system into which the vacuum
pump is to be integrated and by users.

The need for personal safety regulations depends in principle on the
type of use. The operator must provide the users with the necessary
means and must inform his personnel about the dangers emanating
from the processed product.

The operator of the vacuum pump must observe the safety regulations
and must train and instruct his personnel accordingly.

Local regulations regarding the motors and electric control elements
must be observed when installing the pump in potentially explosive
environments.

The maintenance instructions must be followed and observed.

These installation and maintenance instructions must be read and un-
derstood before the vacuum pump is used. If you have any doubts,
contact your Busch representative.

Safety information

The vacuum pump is designed and manufactured in compliance with
the latest technical standards and safety regulations. Nevertheless an
element of residual risk remains.

Various safety instructions are to be found in this handbook and on the
pump. These instructions must be followed. You can recognise these
instructions by the signal words DANGER, WARNING and CAUTION,
which are defined as follows:

DANGER

Disregard of this safety instruction will always result in death, se-
rious injuries or severe damage.

WARNING

Disregard of this safety instruction may result in death, serious in-
juries or severe damage.

CAUTION

Disregard of this safety instruction may result in minor or moderate
injuries or damage.

Safety

BC 0200 F

Page 6

0870767417 (En)

Содержание COBRA BC 0200 F

Страница 1: ...Instructions Screw Vacuum Pumps COBRA BC 0200 F Busch Manufacturing Korea Ltd 189 51 Soicheon ro Majang myun Icheon si Gyunggi do 467 813 Republic of Korea 0870767417 190605 Original instructions Subj...

Страница 2: ...tions on operation 14 Application 14 Switching the vacuum pump on off 15 First start up of the system 15 Switching the system off 15 Maintenance 15 Maintenance program 16 Weekly 16 Monthly 16 Yearly 1...

Страница 3: ...racket OFP Oil filler plug OSG Oil sight glass PS Discharge pressure switch CAO Extracting ventilator CPC PLC connection ES Emergency stop button EMO MB On Off switch Main circuit breaker RC LCD DGF D...

Страница 4: ...BC 0200 F Page 4 0870767417 En MB CPC DPS DGF DGR2 DGR1 PSA TS CWR CWM VFD...

Страница 5: ...not suitable for continuous duty at a pressure more or equal than 150 hPa mbar Caution the operating cycle of 150 hPa mbar must not exceed more than 5 min For other applications contact your Busch rep...

Страница 6: ...valve optional at the exhaust traps the condensate in the pump when the pump is switched off The LCD controller processes the data of the sensors see chapter Communication with the equipment as follo...

Страница 7: ...ntact exceed the limits in Table A5 1 of Appendix 5 SEMI S2 guideline Lock Out Tag Out procedure Type 1 of electrical work l Stop the pump with the remote control or with the stop button press on STOP...

Страница 8: ...ie the contactors open and remove power to motor S Cooling water flow low Water flowmeter B2 Depends on alarm function set in the PLC for water flow Set at factory General Stop ie the contactors open...

Страница 9: ...aws Appliance after warehousing Prior to reoperate a vacuum pump which remained outside the buiding for a certain period of time make sure to let it stand at ambient tempe rature in a room for a whole...

Страница 10: ...l must be disposed of in accordance with local and national regulations This handbook is contained in the delivery package Storage Temporary storage l Make sure that the intake and exhaust flanges are...

Страница 11: ...by the adjustment stroke 15 mm of the four machine foots l Make sure that the four rollers do not touch the ground NOTE In order to ensure the fixation of the pump to the ground it is possible to use...

Страница 12: ...nnection diameter 3 8 NPT Nitrogen connection The nitrogen is connected with a pipe leakproof against oxygen Connection diameter 1 4 NPT Electrical connection Checks l Make sure that the regulations o...

Страница 13: ...e installation handbook is of informative nature only Check the oil level with the help of the oil sight glass OSG on the vacuum pump CAUTION Before you change the type of oil make sure that the new t...

Страница 14: ...tain quantity of liquid If the pump has sucked in liquid a short drying time is necessary at the end of the procedure The allowed maximum inlet gas temperature depends on the inlet pres sure and the t...

Страница 15: ...minated with foreign materials that are dangerous to health the oil and condensates will also be contaminated These foreign materials can infiltrate the pores recesses and other internal spaces of the...

Страница 16: ...essary l Check the seals and replace if necessary l Check the intake and discharge lines and clean or replace if necessary Every 16 000 hours of operation at the latest after 4 years l Drain the oil s...

Страница 17: ...the sealing washer of the magnetic plug is not damaged replace it if necessary l Refit the magnetic plug and tighten up l Make sure that the sealing washer on the drain plug is undamaged and correctly...

Страница 18: ...that the various protective elements stoppers or adhesive tapes have been removed l Switch on the vacuum pump by following the procedure described in the chapter Installation and start up Dismantling...

Страница 19: ...ntaminated or polluted oil can lead to hazardous pump conditions which could cause personal injury Oil quantity The quantity of oil specified in the following table is of informative nature only Check...

Страница 20: ...Nominal motor speed min 1 4570 Noise level EN ISO 2151 dB A 60 Ambient temperature C F 10 40 32 104 Maximal counter pressure Discharge bar 0 2 Cooling water requirement l min min 2 0 Cooling water pr...

Страница 21: ...and electronic equipment and following the standards Standard Title of the standard EN ISO 12100 2010 Safety of machinery Basic concepts general principles of design EN ISO 13857 2008 Safety of machi...

Страница 22: ...Note...

Страница 23: ...Note...

Страница 24: ...myun Icheon si Gyunggi do 467 813 Republic of Korea Phone 82 31 645 2700 Fax 82 31 631 2898 e mail busch busch co kr Malaysia Busch Malaysia Sdn Bhd 4 6 Jalan Taboh 33 22 Seksyen 33 Shah Alam Technolo...

Отзывы: