TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL
24
Parameters in main on-screen menus.
1. Alarm number
- Displays a possible
error occurred during boiler operation.
The error message goes off once the
respective parameter that evoked the
error message returns to its limits.
2. Working Mode
- Indicates the actual
operation mode of the boiler.
2.1 Modes of operation:
2.1.1 OFF
- the boiler is in standby mode,.
2.1.2 IGNITION
- The boiler is in firing-
up mode. The controller follows the
„O2
VALUE ON IGNITION“
parameter value
and once it drops below the preset value,
it shifts into „Burn On“ mode.
2.1.3 Burn On
- The boiler is in ignition
mode. The controller monitors the
temperature and oxygen content of
exhaust gases, and depending on the
values entered shifts into normal working
mode.
2.1.4 Work
- The boiler is in normal
operating mode. The controller monitors
the temperature of coolant in boiler and
the exhaust gases. It also monitors the
oxygen level of exhaust gases and controls
the primary and secondary air intake
flaps.
2.1.5 Burn Out
- The boiler has entered
extinction mode. The boiler goes into
this mode upon exhaustion of fuel and
increase of oxygen level in the exhaust
gases above the preset limit value.
2.1.6 Glow
- This is the process of
sustaining the glow bed inside the boiler.
The controller switches to this mode when
exhaust gas temperature decreases.
3. BOILER TEMPERATURE
- Displays the
temperature inside the boiler water
jacket.
4. EXHAUST TEMPERATURE
- Shows the
temperature of exhaust gases inside the
chimney.
5. O2 VALUE
- Displays the actual value of
oxygen content in exhaust gases.
6. BOILERDOOR
- Indicates whether the
boiler door is open or not (open / close).
VALVE PRIMARY
- Shows in percentage
how wide is open the primary air flap.
VALVE SECUONDARY
- Shows in
percentage how wide is open the
secondary air flap.
EXHAUST FAN
– Shows in percentage the
performance rate of the suction fan.
BUFFER TOP
- Displays the temperature
at the top part of the buffer tank. (This
parameter is active only when the
selected system layout includes a buffer
tank.)
BUFFER BOTTOM
- Monitors and displays
the temperature at the bottom of the
buffer tank. (This parameter is active only
when the selected system layout includes
a buffer tank.)
WATER HEATER
- Monitors and displays
the temperature inside the domestic
hot water tank. (This parameter is active
when selected system layout includes
domestic hot water tank.)
Explanation of on-screen parameter
menus