63
107672-03 - 5/18
VII. Venting
I. Assembly of Stainless Steel Vent Systems
1.
This boiler has been listed for use with Duravent FasNSeal Flex Stainless Steel vent systems to be provided
by the installer.
2.
The vent adaptor has three different inside diameters. The smaller, lower diameter accepts 3” Stainless steel
(Figure 7.27). A locking band clamp in the adaptor prevents the vent pipe from coming out of the adaptor
once it is installed and tightened. Lubricate the upper gaskets in the vent adaptor with water and insert the
first piece of 3” stainless into the adaptor until it bottoms out. Tighten locking band clamp to secure vent
pipe.
3.
Installation of Air Intake System - Start assembly of the PVC air intake system at the boiler. Assembly of the
air intake system is done in the same manner as the vent system except as follows:
a. Drill a 7/32” clearance hole into the front side of the air intake adaptor. Insert the first piece of PVC air
intake pipe into the air intake connection and drill a 1/8” tap hole into the PVC which lines up with the 7/32”
clearance hole and secure them together with a #10 x 1” sheet metal screw. Seal the joint between the intake
pipe and the adaptor with RTV.
b. All intake piping may be PVC.
c. There is a 0” minimum clearance between the air intake piping and all types of construction.
d. To the extent possible, pitch horizontal air intake piping towards the outside.
4.
Installation using DuraVent FasNSeal Flex (Option 39)
Refer to manufacturer’s instructions for assembly of all flex components including the chimney cap and
adaptor to rigid pipe at base of masonry chimney. In addition, observe the following requirements:
a. Refer to the appropriate Vent option in table 7.21 for a list of the principle flex components required. Rigid
vent pipe by the same manufacturer will also be required for the run from the boiler to the base of chimney.
b. Masonry chimneys cannot be used for an air chase.
Asphyxiation Hazard. Follow these instructions and the installation instructions
included by the original stainless steel venting component manufacturer DuraVent. Failure to do so
could cause products of combustion to enter the building, resulting in severe property damage, personal
injury or death. Where a conflict arises between DuraVent or instruction and these instructions, the more
restrictive instructions shall govern.
Do not mix vent components from listed manufacturers.
Examine all components from listed manufacturers.
All all components from listed manufacturers.
Asphyxiation Hazard. Vent systems made by Duravent rely on gaskets for proper sealing.
When these vents systems are used, take the following precautions:
•
Make sure that gasket is in position and undamaged in the female end of the pipe
•
Make sure that both male and female pipes are free of damage prior to assembly.
•
Only cut vent pipe as permitted by the vent manufacturer in accordance with their instructions
When pipe is cut, the cut end must be square and carefully de-burred prior to assembly.
NOTICE
The venting system must be free to expand and contract and supported in accordance with the
installation instructions included by the original stainless steel venting component manufacturer.
WARNING
WARNING
I. Assembly of Stainless Steel Vent Systems
Содержание K2WT Residential
Страница 11: ...11 107672 03 5 18 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 78: ...78 107672 03 5 18 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 86: ...86 107672 03 5 18 Figure 10 5 J3 Field Wiring Figure 10 4 4 20 mA EMS Field Wiring X Wiring continued ...
Страница 88: ...88 107672 03 5 18 X Wiring continued Figure 10 7 Internal Ladder Diagram ...
Страница 89: ...89 107672 03 5 18 PAGE LEFT INTENTIONALLY BLANK ...
Страница 90: ...90 107672 03 5 18 X Wiring continued ...
Страница 91: ...91 107672 03 5 18 Figure 10 8 Internal Wiring Connections Diagram X Wiring continued ...
Страница 93: ...93 107672 03 5 18 Figure 10 9 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 94: ...94 107672 03 5 18 X Wiring continued Figure 10 10 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 103: ...103 107672 03 5 18 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 148: ...148 107672 03 5 18 XV Service Parts continued ...
Страница 152: ...152 107672 03 5 18 XV Service Parts continued ...
Страница 154: ...154 107672 03 5 18 XV Service Parts continued 85 86 91 95 ...
Страница 163: ...163 107672 03 5 18 ...
Страница 164: ...164 107672 03 5 18 ...
Страница 165: ...165 107672 03 5 18 ...
Страница 166: ...166 107672 03 5 18 ...
Страница 167: ...167 107672 03 5 18 ...
Страница 168: ...168 107672 03 5 18 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...