XIII. Service and Maintenance
(continued)
Refer to Section VII “Venting” to re-assemble any vent system components that are disassembled during this
inspection and for details on supporting, pitching, and terminating the vent system.
s.
Replace any wiring
which has been disconnected.
t.
Inspect the hydronic system.
Look for leaks and repair any found. If system contains antifreeze, or
other additives, test and/or maintain them as directed by the additive manufacturer. Refer to Section
XI. “Start-up and Checkout” for important information on boiler water and the use of boiler water
additives.
u.
Test the flow switch.
To do this:
• Start with the boiler in standby.
• Either close a shut-off in the boiler loop or unplug the boiler pump at connector L1. (see Figure
10.8)
• Initiate a call for heat and confirm that the boiler shows an Active Fault indicating that the flow
switch is open.
v.
Follow ALL instructions in
Section XI “Start-up and Checkout” to place the boiler back in service,
including the performance of a combustion test.
NOTICE
Do not remove return pipe connection from heat exchanger to service the circulator.
If burner comes on with no flow through the boiler, there is a problem with the flow
switch. Turn the boiler off immediately. Failure to do so could cause severe heat exchanger damage.
CAUTION
Содержание K2WT Residential
Страница 11: ...11 107672 03 5 18 Figure 5 1 Wall Layout Mounting Hole Location V Mounting The Boiler continued ...
Страница 78: ...78 107672 03 5 18 Figure 9 6 Piping Method 1 Near Boiler Piping Shaded Boiler Loop IX System Piping continued ...
Страница 86: ...86 107672 03 5 18 Figure 10 5 J3 Field Wiring Figure 10 4 4 20 mA EMS Field Wiring X Wiring continued ...
Страница 88: ...88 107672 03 5 18 X Wiring continued Figure 10 7 Internal Ladder Diagram ...
Страница 89: ...89 107672 03 5 18 PAGE LEFT INTENTIONALLY BLANK ...
Страница 90: ...90 107672 03 5 18 X Wiring continued ...
Страница 91: ...91 107672 03 5 18 Figure 10 8 Internal Wiring Connections Diagram X Wiring continued ...
Страница 93: ...93 107672 03 5 18 Figure 10 9 TACO SR504 or Equivalent Zone Panel Wiring Connection Diagram X Wiring continued ...
Страница 94: ...94 107672 03 5 18 X Wiring continued Figure 10 10 Sage Zone Control Circulator Panel Wiring Connection Diagram ...
Страница 103: ...103 107672 03 5 18 Lighting and Operating Instructions XI Start Up and Checkout continued ...
Страница 148: ...148 107672 03 5 18 XV Service Parts continued ...
Страница 152: ...152 107672 03 5 18 XV Service Parts continued ...
Страница 154: ...154 107672 03 5 18 XV Service Parts continued 85 86 91 95 ...
Страница 163: ...163 107672 03 5 18 ...
Страница 164: ...164 107672 03 5 18 ...
Страница 165: ...165 107672 03 5 18 ...
Страница 166: ...166 107672 03 5 18 ...
Страница 167: ...167 107672 03 5 18 ...
Страница 168: ...168 107672 03 5 18 U S Boiler Company Inc P O Box 3020 Lancaster PA 17604 1 888 432 8887 www usboiler net ...