background image

7

Clearance to Combustibles

The  distance  to  be  maintained  from  the  surfaces  of  the 

fireplace to combustibles must be observed. Below is a list of 

the most common  combustible materials to name a few:

Drywall 

Wood flooring 

 

Plywood

Sub-flooring 

Wood Framing   

Particle board

Mill board 

Plywood paneling

Maintain the following minimum clearances:

Unit front, sides, rear

0” 

0

Combustible floor

0”

0

Sheathing or trim to opening sides

8” (203 mm)

Combustible sheathing above opening top

8” (203 mm)

Mantel above opening

12” (305 mm)

Opening to side wall

20” (508 mm)

Insulation from firebox

0”

0

Due  to  high  temperatures,  never  install  this  fireplace  in  a 

recreational  vehicle,  in  high  traffic  areas,  drafty  areas,  or 

where curtains, furniture, clothing, or other flammable objects 

are less than 36” from the front or side and 42” from the top of 

the fireplace.

CAUTION: This gas fireplace attains high temperatures. Keep 

children and adults away from hot surfaces to avoid ignition of 

clothing and/or burns. Even after the fireplace is shutdown it 

will remain hot for a time afterward. Allow the surface to cool 

before touching it.

Carefully supervise young children when they are in the room 

with the fireplace.

All  fireplace  openings  for  both  combustion  air  and  exhaust 

must  remain  open  and  unobstructed  at  all  times  when  the 

fireplace is in operation.

  The Burntech® fireplace has been designed, tested and 

approved for zero clearance to combustible floors.

  Be certain that the Burntech® fireplace is installed with the 

finished fire brick floor of the fireplace so that it is at least 4-1/2” 

(four and a half inches) above the combustible floor system.

Warning to the structural engineer and/or building contractor: 

It is your responsibility to be certain that the fireplace can be 

properly supported by the combustible floor system on which 

the fireplace will rest. Be advised that this engineering equation 

will be in addition to any live or dead weights that the floor has 

to carry.

Burntech® Fireplace & Chimney Systems

Before Getting Started…
  Even  if  you  consider  yourself  an  expert  in  the  field  of 

fireplace installation, we at 

Burntech®

 caution you to take the 

time  to  totally  familiarize  yourself  with  the  instructions  to 

follow.
 

We can assure you that there will be information that will 

make  the  installation  go  smoother  and,  above  all,  safer,  for 

everyone concerned. At the least, reading these procedures will 

save you time and, at the most, it will prevent any malfunction 

that could result in property damage or serious injury.
 

Do not start the installation until you have checked out all 

the local, regional, state and national rulings, laws and codes 

as they apply to fireplaces and fireplace installations. Every 

community  is  different  so  do  not  assume  that  because  you 

know the requirements for one locality, it will be the same in 

the next. Avoid bureaucratic hassles and do your homework 

WELL BEFORE you start your project! 

The  Burntech®  gas  fireplace  is  designed  to  be  installed 

with 

properly sized 

B-vent metal chimney 

or "Class A"

 UL 

103  chimney.

  BVent  chimney  or  “Class  A”  chimney 

systems  must  be  used  on  all  Burntech  BVent  Fireplace 

systems. 

Note that the chimney system must always vent 

to the outside of the building.
This Burntech® fireplace is intended as a supplemental heat 

source only. It is not intended as a primary heat source.
It  is  the  responsibility  of  the  contractor  installer  (not  the 

manufacturer)  to  ensure  that  adequate  combustion  air  is 

provided  for  proper  function  of  this  fireplace.  Fireplaces 

take up a large volume of replacement air from outside the 

house  and  if  the  house  is  of  airtight  construction,

 

dangerous

 

gas

  spillage  may  occur  if  proper  draft  is  not 

achieved.

There  are  many  conditions  beyond  a  manufacturer’s 

control  when  it  comes  to  the  operation  of  the  fireplace. 

The manufacturer cannot be responsible for 

spillage free

 

operation,  nor  can  the  manufacturer  take  on  the 

responsibility  for  problems  with  surrounding  construction; 

chimneys  that  have  not  been  built  at  the  right  heights; 

system  drafts  caused  by  faulty  mechanical  systems; 

adverse  weather  conditions  or  any  other  inclement 

environmental situations

Inspect  all  fireplace  &  chimney  components  for  evidence 

of damage prior to starting installation. Consult your local 

distributor for replacement parts if necessary.
Under no circumstances should you make any adjustments 

or  modifications  to  the  chimney  system  during  the 

installation  procedure.  If  you  do,  you  are  not  only  liable 

for negating the warranty, but you could very well cause a 

serious malfunction of the fireplace. You must follow these  

chimney  instructions.

Chimney System Heights

When installed, the maximum overall height of the Fireplace is 

40’-0”  (forty  feet).  The    minimum  installed  height  of  the 

completed  fireplace  is  14’  0”  (fourteen  feet),  given  that  the 

chimney is straight. If the chimney includes one or more offset 

sections, the measurement is 17’ 0” (seventeen feet).

1)

2)

3)

4)

5)

6)

Содержание GBVS 39/44/49

Страница 1: ...0 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The instal...

Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 3: ...YPE DO NOT REMOVE THIS LABEL See Burntech Installation Operating Instructions for this model Contact local building officials about restrictions and installation specifications in your area THIS FIREP...

Страница 4: ...ponents Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury...

Страница 5: ...DESCRIPTION QTY 1 TFS39 1 TFS44 1 TFS49 1 HEARTH Left or Right 2 2 TFS39 2 TFS44 2 TFS49 2 REAR WALL 3 3 TFS39 3 TFS44 3 TFS49 3 SIDE WALL 7 3A TFS39 3A TFS44 3A TFS49 3A SIDE WALL with 4 opening for...

Страница 6: ...ent parts and accessories as listed in these parts lists Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending u...

Страница 7: ...illustrations in this manual are for general reference only Do not scale drawings Actual design elements will vary from case to case Pay attention to specified minimum clearances to combustibles WARNI...

Страница 8: ...accessories Use of other controls parts and accessories which are not designed for use with Burntech gas fireplaces is prohibited and will void all warranties certifications listings and building code...

Страница 9: ...t reading these procedures will save you time and at the most it will prevent any malfunction that could result in property damage or serious injury Do not start the installation until you have checke...

Страница 10: ...he addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight o...

Страница 11: ...at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resulting from L D Note that Burntech cannot accept respons...

Страница 12: ...washers GBVS 44 49 Eight 8 pieces 3 8 rebar x 36 long included with unit Eight 8 ea All thread x 12 long with nuts and washers ALL UNITS Three 3 90 lb bags of ready mix concrete with 1 4 or smaller ag...

Страница 13: ...latness level if necessary Figure 13 1 2 away from edges 1 2 mortar bead typical Hearth section shown prepared for Right Side position Apply mortar bead to all mating surfaces Apply mortar to the rema...

Страница 14: ...veled face lines up with the inward angles of the lintel sides Resulting top surfaces should be level Figure 20 Lower Dome Sides Rating Plate faces inside Verify that the smoke dome side front and rea...

Страница 15: ...5 Fireplace Finishes Combustible Trim Clearances Mantel and Mantel Shelf Clearances As with any radiant heat fireplaces all Burntech Fireplaces must comply with building code safety clearances per uni...

Страница 16: ...in an accident or malfunction If instructions are not followed the warranty on the product will become null and void 3 1 2 3 4 5 Note that the most important aspect of the installation is the maintena...

Страница 17: ...1 One elbow begins the installation procedure and the second elbow is used to finish off each section In all likelihood a 30 degreeoffsetelbowwillprobablybethefirsthardwareusedoff the top of the ancho...

Страница 18: ...lination Multiple offsets are permitted if they do not exceed a 45 inclination The total lengths of the two offsets are not required to meet the 75 allowable rule Figure 2 Example 3 Shows a single off...

Страница 19: ...re scheduled to install the round top termination unit or any of the flashings or flues that will be exposed to outside weather conditions Venting terminals shall not be recessed into walls or siding...

Страница 20: ...ch sensor pointed toward the room out of the fireplace Use six 6 drywalls screws to fasten it in place on the front most part of the firebox ceiling as shown through the six 6 pre drilled holes Attach...

Страница 21: ...SOAPY WATER SOLUTION IF A LEAK IS DETECTED TIGHTEN CONNECTIONS AND TEST AGAIN NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS Insert a one way screw into the hole in the front of each bracket and tight...

Страница 22: ...d the heat chambers facing the back of the fireplace Figure 35 Place the front log on the grate in front of the top burner pipe with the flat down and the heat chambers toward the burner pipe and the...

Страница 23: ...the four 4 screws above and below the control panel face then pull the control panel out far enough to expose the test ports on the valve Figure 41 Unscrew the port marked IN part way and test CAUTION...

Страница 24: ...ts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads a...

Страница 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Страница 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 27: ...ded at Burntech Fireplace Solutions s option Nothing in this warranty makes Burntech Fireplace Solutions or any affiliate thereof liable in any respect for any injury or damage to the building or stru...

Отзывы: