Specifying Chimney Heights

 

If the horizontal distance from the mid-point of the chimney 

to the peak of the roof ridge is less than 10 feet, the top of the 

chimney must be at least 2 feet above the roof ridge. This is 

called the “2 foot in 10 foot” rule.

 

If  the  horizontal  distance  from  the  chimney’s  center 

measured across to the ridge of the roof is more than 10 feet, 

the top of the chimney still needs to be at least 2 feet above a 

point measured from a distance of 10 feet horizontally along 

the roof.

Figure 3

 

Though  there  are  many  configurations  in  meeting  these 

requirements, chimney height cannot be less than 3 feet above 

the roof at the edge of the chimney.

 

If the roof is flat, the chimney must extend no less than 3 

feet from where it intersects the roof. If the chimney is entering 

the  roof  at  an  angle,  measure  the  shorter  angle  where  the 

chimney intersects the roof which should be at least 3 feet.

Note:

 The previous guidelines do not take into consideration     

outside  conditions  which  may  require  a  higher  chimney  due 

to foliage, other buildings, power lines and weather conditions 

in  your  area.  Follow  the  chimney  manufacturer’s  installation 

guide for further information.

Chimney Termination Units

 

You  will  be  installing  at  or  possibly  near  the  top  of  the 

chimney chase flashing. A top termination unit is the essential 

piece of equipment in keeping sparks out of the atmosphere. 

Before installing this important piece of equipment, you will have 

to make a judgment call as to whether or not the termination 

unit – like all the other exterior exposed chimney components, 

for that matter – should be painted in order to protect it/them 

from rusting and weathering. Particularly if you are installing 

the fireplace and chimney near water or in a high humidity area, 

the  manufacturer  recommends  a  top  quality,  rust-proof  paint 

especially formulated for metal. Follow the paint manufacturer’s 

directions, applying the paint well before you are scheduled to 

install the round top termination unit or any of the flashings or 

flues that will be exposed to outside weather conditions.

 

Venting terminals shall not be recessed into walls or siding. 

This appliance, when installed, must be electrically grounded 

in  accordance  with  local  codes  and  in  the  absence  of  local 

codes, with the National Electrical Code, ANSI NFPA 70, or the 

Canadian Electrical Code, CSA C22.1.

Important Pre-installation Information

  Before you begin, review the information and safeguards 

below  regarding  the  installation  and  operation  of  the  gas 

Fireplace.

  This fireplace may only be connected to the gas supply 

listed on the label.

 Never use propane gas in a gas fireplace 

designed  for  natural  gas  or  natural  gas  in  a  gas  fireplace 

designed for use with propane gas.

  The  gas  fireplace  must  be  installed  by  an  BURNTECH 

Certified or other qualified professional installer. The installation, 

including  provisions  for  combustion  and  ventilation  air,  must 

conform  with  local  codes,  or,  in  the  absence  of  local  codes, 

with  the  latest  edition  of  the  National  Fuel  Gas  Code, ANSI 

Z223.1, and NFPA54.

The  fireplace  must  have  a  gas  supply  line  that  has 

been installed by a qualified technician in accordance with 

all local codes. 

The gas supply line must be 1/2” minimum interior diameter. If 

the gas line to the fireplace is longer than 5’, a larger diameter 

line may be necessary.

BURNTECH

Supplied

B

urner P/N

BTU*

x 1000

Orifice Drill 

Size 

(top/front)

Fireplace

Model #

Nat

LP

GML-24-01(N)(P)

60

28/48 47/56 GBVS-39 or 

-44

GML-30-01N

90

19/41

GBVS-49

GML-30-01P

84

40/55

*Nominal BTU based on gas inlet pressure. Nominal gas inlet

pressure for natural gas is 5” W.C.

WARNING: THIS FIREPLACE IS DESIGNED FOR USE ONLY 

WITH THE ANSI Z21.50 DECORATIVE GAS LOGS AND 

BURNER TESTED AND APPROVED FOR THIS FIREPLACE. 

Any change or alteration in burners or log sets must be 

approved by Burntech in writing or warranty will be void. 

BTU's can never exceed more than 65,000 on Models GBVS 

39 and 44 and 80,000 btu's on Model GBVS 49. Unapproved 

changes or alterations could result in a fire or explosion 

resulting in property damage, personal injury or death.

Содержание GBVS 39/44/49

Страница 1: ...0 standard Solid fuels shall not be burned in this fireplace This appliance must be vented vertically through the roof This appliance is not for installation in manufactured or mobile homes The instal...

Страница 2: ...THIS PAGE INTENTIONALLY LEFT BLANK...

Страница 3: ...YPE DO NOT REMOVE THIS LABEL See Burntech Installation Operating Instructions for this model Contact local building officials about restrictions and installation specifications in your area THIS FIREP...

Страница 4: ...ponents Warning Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury...

Страница 5: ...DESCRIPTION QTY 1 TFS39 1 TFS44 1 TFS49 1 HEARTH Left or Right 2 2 TFS39 2 TFS44 2 TFS49 2 REAR WALL 3 3 TFS39 3 TFS44 3 TFS49 3 SIDE WALL 7 3A TFS39 3A TFS44 3A TFS49 3A SIDE WALL with 4 opening for...

Страница 6: ...ent parts and accessories as listed in these parts lists Before beginning installation be sure the burner system is complete by comparing its contents with this Parts List Parts may differ depending u...

Страница 7: ...illustrations in this manual are for general reference only Do not scale drawings Actual design elements will vary from case to case Pay attention to specified minimum clearances to combustibles WARNI...

Страница 8: ...accessories Use of other controls parts and accessories which are not designed for use with Burntech gas fireplaces is prohibited and will void all warranties certifications listings and building code...

Страница 9: ...t reading these procedures will save you time and at the most it will prevent any malfunction that could result in property damage or serious injury Do not start the installation until you have checke...

Страница 10: ...he addition of floor joists to align with the anchor brackets allows the brackets to be directly connected to the floor joists Note that additional floor joists may be required to support the weight o...

Страница 11: ...at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted for the deflection resulting from L D Note that Burntech cannot accept respons...

Страница 12: ...washers GBVS 44 49 Eight 8 pieces 3 8 rebar x 36 long included with unit Eight 8 ea All thread x 12 long with nuts and washers ALL UNITS Three 3 90 lb bags of ready mix concrete with 1 4 or smaller ag...

Страница 13: ...latness level if necessary Figure 13 1 2 away from edges 1 2 mortar bead typical Hearth section shown prepared for Right Side position Apply mortar bead to all mating surfaces Apply mortar to the rema...

Страница 14: ...veled face lines up with the inward angles of the lintel sides Resulting top surfaces should be level Figure 20 Lower Dome Sides Rating Plate faces inside Verify that the smoke dome side front and rea...

Страница 15: ...5 Fireplace Finishes Combustible Trim Clearances Mantel and Mantel Shelf Clearances As with any radiant heat fireplaces all Burntech Fireplaces must comply with building code safety clearances per uni...

Страница 16: ...in an accident or malfunction If instructions are not followed the warranty on the product will become null and void 3 1 2 3 4 5 Note that the most important aspect of the installation is the maintena...

Страница 17: ...1 One elbow begins the installation procedure and the second elbow is used to finish off each section In all likelihood a 30 degreeoffsetelbowwillprobablybethefirsthardwareusedoff the top of the ancho...

Страница 18: ...lination Multiple offsets are permitted if they do not exceed a 45 inclination The total lengths of the two offsets are not required to meet the 75 allowable rule Figure 2 Example 3 Shows a single off...

Страница 19: ...re scheduled to install the round top termination unit or any of the flashings or flues that will be exposed to outside weather conditions Venting terminals shall not be recessed into walls or siding...

Страница 20: ...ch sensor pointed toward the room out of the fireplace Use six 6 drywalls screws to fasten it in place on the front most part of the firebox ceiling as shown through the six 6 pre drilled holes Attach...

Страница 21: ...SOAPY WATER SOLUTION IF A LEAK IS DETECTED TIGHTEN CONNECTIONS AND TEST AGAIN NEVER USE AN OPEN FLAME TO CHECK FOR GAS LEAKS Insert a one way screw into the hole in the front of each bracket and tight...

Страница 22: ...d the heat chambers facing the back of the fireplace Figure 35 Place the front log on the grate in front of the top burner pipe with the flat down and the heat chambers toward the burner pipe and the...

Страница 23: ...the four 4 screws above and below the control panel face then pull the control panel out far enough to expose the test ports on the valve Figure 41 Unscrew the port marked IN part way and test CAUTION...

Страница 24: ...ts a Check with a millivolt meter Should be 250 millivolts or more b Pilot flame making a blowing sound b Pilot needs adjusting see Checking and Adjusting the Pilot on page 22 c Generator wire leads a...

Страница 25: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Страница 26: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 27: ...ded at Burntech Fireplace Solutions s option Nothing in this warranty makes Burntech Fireplace Solutions or any affiliate thereof liable in any respect for any injury or damage to the building or stru...

Отзывы: