18
Spareparts
Type 2380
Malfunction
Cause / remedial action
Control quality
dissatisfying
E.g. caused by changed pressure conditions, etc.
→
Adjust the controller via function
X.TUNE
→
Check an adjust the dead band (see also
operating instructions for Type 869x)
→
When control air leakage occurs: see
respec tive operating instructions
Bus communi-
cation doesn't
work correctly
Missing or incorrect data transfer
→
Check (and correct if necessary) the settings
for bus interface at the device and check also
the right version of the EDS file (DeviceNet)
or GSD file (Profibus).
→
See also the respective operating in struc-
tions of the controller Type 869x used for
correct installation, configuration and start-up
Serial commu-
nica tion with
software
"Com muni-
cator" doesn't
work correctly
Missing or incorrect data transfer
→
Use the same settings of serial interface
at the device and in the „Communicator“
software
For best compatibility and device support
→
Use the current version of the software
„Communicator“ (Type 8920 - download
from the Bürkert website)
Tab. 1: Malfunction / troubleshooting
12.
SPARE PARTS
12.1. Safety instructions
WARNING!
Risk of injury when opening the actuator!
The actuator contains a tensioned spring. If the actuator is
opened, there is a risk of injury from the spring jumping out!
▶
The actuator must not be opened.
CAUTION!
Risk of injury and/or damage by the use of incorrect parts!
Incorrect accessories and unsuitable spare parts may cause
injuries and damage the device and the surrounding area.
▶
Use only original accessories and original spare parts from
Bürkert.
12.2. Spare part sets
The bellow and 2 O-rings are available as a spare part set.
Consider the right size of the bellow according to the type label -
see the order table below.