8205
E-23-
pH CONTROLLER 8205
ENTER
ENTER
0......9
0......9
ENTER
ENTER
ENTER
0......9
0......9
ENTER
OUTPUT 2
SETPOINT
PWM 2
T2
=
000,0S
PULSE 2
SETPOINT
000 / MIN
012 / MIN
T2
=
012,3S
T2
=
000,0S
T2
=
001,5S
(T2( s)+ 0,02(s)) x F2 < 60
Internal checking of this condition
is provided. If this is not, the
program returns to T2 selection
until complying with the required
condition.
Impulse
Duration
(T2 s)
Impulse
Frequency
(F2)
Impulse
Duration
(T2 s)
4.3.5 Output 2 (Acid)
Select the controller output 2 logic signal.
Impulse time selection (PULSE 2)
Set the duration of each impulse and the maximum frequency of the output signal.
Impulse frequency selection (PWM2)
Set the frequency of the logic output signal activation.
4 OPERATION
!
If the pulse output is provided by a relay; set F2 < 60. (cf § 2.5)