5
Installation
Logano plus SB325 – 6 720 806 328 (2013/07)
24
▶ Hook the lower front panel section with the four hooks [1] into the
slots to the left and right on the side panels.
▶ Insert the upper front panel with its hooks [2] into the slots on the
lower front panel, and hook the top into the front boiler cover [3].
Fig. 26 Fasten lower and upper front panels
[1]
Hook lower front panel
[2]
Hook upper front panel
[3]
Hooking the upper front panel into the boiler cover
5.10 Opening and reversing the combustion chamber door
The combustion chamber door can be moved from the right-hand side
(factory-set) to the left-hand side.
5.10.1 Opening and closing the combustion chamber door
Opening the combustion chamber door
▶ Undo two screws on the combustion chamber door.
▶ Open the combustion chamber door.
Fig. 27 Opening the combustion chamber door
[1]
Hinge pin
[2]
Dowel pin
Closing the combustion chamber door
▶ Close the combustion chamber door.
▶ The complete gasket must be pressed centrally onto the middle of the
combustion chamber.
Check it has been fitted correctly by using chalk or a similar material
to make a mark.
▶ Fit two screws in the combustion chamber door.
▶ Tighten the screws with a torque of 25 Nm.
5.10.2 Refitting the door hinges
As standard, the combustion chamber door opens from left to right. The
following instructions assume the standard direction.
If required, due to space restrictions, the combustion chamber door can
be converted to open to the left.
▶ Open the combustion chamber door.
▶ Pull the hinge pin (
Fig. 27, [1]) out of the hinge.
▶ Hook combustion chamber door with dowel pin [2] into lower hinge
bracket and secure in upper hinge bracket with hinge bolt [1].
▶ Close the combustion chamber door.
▶ Fit two screws in the combustion chamber door with washers.
▶ Tighten the screws with a torque of 25 Nm.
5.11 Fitting the burner (accessory)
Fit third party burners in accordance with the installation
instructions of the burner manufacturer. The door stop
can be moved from the right-hand side to the left.
WARNING:
Risk of injury through dropping combustion
chamber door.
▶ Retighten the nuts that secure the combustion
chamber door two weeks after commissioning.
WARNING:
Risk of injury from dropping parts.
While the door hinges are being refitted, there is a risk of
the combustion chamber door dropping.
▶ Refit the door hinges before mounting the burner.
NOTICE:
System damage through incorrect burner.
▶ Only use burners which meet the technical boiler
requirements of Logano plus SB325.
6 720 804 354-13.1ITL
1
2