60
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Troubleshooting
11
Flue gas odour inside the boiler room.
Does flue gas escape around the draught
hood?
Determine and remedy the cause for
insufficient flue draught. Shut the burner
down, if the fault cannot be remedied
immediately.
Negative pressure in the flue pipe >3 Pa?
Is the flue pipe blocked?
Is the size of the chimney OK?
Are fans used in the boiler room, which
extract air from the room (extractor hoods,
dryers …)?
Are deposits or fibre contamination visible
on the heat exchanger surface?
Visual check through the clean-out cover
and combustion chamber.
Clean the boiler dry or, if required, wet.
Operating condition/faults observed
Troubleshooting
Remedy