Specification
4
13
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Boiler
size
Nozzle pressure
LPG
Propane
P (G 31)
Supply pressure
(Flow pressure)
58 - 37
36
35
34
33
32
31
30
29
28
27
kW
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
150 - 375
35
34
33
32
31
30
29
28
27
26
25
Tab. 7
Nozzle pressure for LPG P subject to the supply pressure
Boiler
size
Nozzle pressure
LPG
Butane/propane mixtures
B/P (G 30)
Supply pressure
(Flow pressure)
58 - 37
36
35
34
33
32
31
30
29
28
27
kW
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
mbar
150 - 375
31.5
31.5
31.5
31.5
31
30
29
28
27
26
25
Tab. 8
Nozzle pressure for LPG B/P subject to the supply pressure
Gas throughput
Boiler size
Natural gas
H
(G20)
Natural gas
L
(G25)
LPG
Propane
(G31)
LPG
B/P
(G30)
kW
m³/h
m³/h
kg/h
kg/h
150
16.2
18.9
12.6
12.8
175
19.0
22.0
14.7
14.9
200
21.7
25.2
16.8
17.0
225
24.4
28.3
18.9
19.2
250
27.0
31.4
20.9
21.2
275
29.7
34.5
23.0
23.3
300
32.4
37.7
25.1
25.5
325
35.1
40.8
27.2
27.6
350
37.8
44.0
29.3
29.7
375
40.5
47.1
31.4
31.9
Tab. 9
Gas throughput
Содержание Logano GE434