12
We reserve the right to make any changes due to technical modifications.
Commissioning and maintenance instructions Logano GE434 Gas-fired special boiler • Issue 02/2003
Buderus Heiztechnik GmbH • http://www.heiztechnik.buderus.de
Specification
4
4
Specification
1
Relative to 15 °C gas temperature and 1013 mbar air pressure
Specification - Logano GE434 gas-fired special boiler
Boiler size
kW
150
175
200
225
250
275
300
325
350
375
Boiler sections
Num-
ber
2 x 7
2 x 8
2 x 9
2 x 10
2 x 11
2 x 12
2 x 13
2 x 14
2 x 15
2 x 16
Rated
Partial
load
kW
75.0
87.5
100.0
112.5
125.0
137.5
150.0
162.5
175.0
187.5
output
Full
load
kW
150.0
175.0
200.0
225.0
250.0
275.0
300.0
325.0
350.0
375.0
1
Combustion
Partial
load
kW
81.0
94.5
108.0
121.5
134.5
148.0
161.5
175.0
188.5
202.0
output
Full
load
kW
162.0
189.0
216.0
243.0
269.0
296.0
323.0
350.0
377.0
404.0
2
Flue gas
Partial
load
°C
84
72
75
78
76
76
77
91
81
84
temperature
3
Full
load
°C
116
104
110
117
103
109
113
116
121
124
Flue gas
Partial
load
kg/s
0.0798 0.1187 0.1146 0.1197 0.1510 0.1612 0.1671 0.1958 0.2053 0.2090
mass flow rate
Full
load
kg/s
0.0925 0.1382 0.1393 0.1405 0.1903 0.1938 0.1997 0.2398 0.2432 0.2497
CO
2
content
Partial
load
%
4.0
3.1
3.7
4.0
3.5
3.6
3.8
3.5
3.6
3.8
Full
load
%
7.2
5.5
6.3
7.1
5.7
6.2
6.6
5.9
6.3
6.6
Draught
Pa
3
CE designation, boiler
CE-0085 AS 0285
Tab. 5
Specification
1
Alternative for Spain (ES): 370 kW (rated output)
2
Alternative for Spain (ES): 399 kW (combustion output)
3
Acc. to DIN EN 656. The minimum flue gas temperature for the chimney calculation acc. to DIN 4705 is approx. 6 K lower.
Boiler size
Main gas nozzle designation
Rated gas nozzle pressure
1
kW
Natural gas
H
(G20)
Natural gas
L
(G25)
LPG
Propane
P
(G31)
LPG
B/P
(G30)
Natural gas
H
(G20)
mbar
150 - 375
295
340
190
180
14
Tab. 6
Main gas nozzle and rated gas nozzle pressure
Содержание Logano GE434
Страница 71: ...71 14 Declaration of conformity ...