Commissioning the heating system
8
Logano GB125 oil condensing boiler - Technical specifications are subject to change without prior notice.
39
8.2
Checking the location of the hot gas baffle plates
Prior to commissioning check that the hot gas baffle pla-
tes are horizontally positioned.
B
Pull the power plug from the SAFe.
B
Open the burner door by removing the two hexagon
side bolts.
B
Slightly pull the hot gas baffle plates out of the hot
gas flues.
B
Position the hot gas baffle plates horizontally and
push them into the hot gas flues.
B
Close the burner door and secure with the two hexa-
gon bolts (tighten to approx. 10 Nm). Tighten the he-
xagon bolts evenly to properly seal the burner door.
B
Attach the power plug to the SAFe.
8.3
Preparing the heating system for
operation
B
Turn on the fuel supply at the main shut-off valve.
B
Switch on the heating system emergency stop switch
(if installed) and/or insert/set the corresponding do-
mestic fuse/circuit breaker.
Fig. 36
Opening the burner door
1
Hot gas baffle plates in the hot gas flues
1
BOILER DAMAGE
Never remove or reposition the hot gas
baffle plates.