Installing the boiler
7
Logano GB125 oil condensing boiler - Technical specifications are subject to change without prior notice.
30
7.4.1 Fitting the condensate drain set
B
Route the condensate drain between the condensate
drain connector and siphon with a slope to prevent
the condensate from flowing back into the boiler.
B
Trim the condensate hose to size and secure with a
hose clip.
B
Connect the siphon outlet with the drain using a con-
densate hose.
7.5
Making the water connections
7.5.1 Fitting the return connector
Connection with the heating circuit quick assembly system (accessory)
B
Fit the return connector with inserted flat gasket to
connection RK/RS.
B
If no DHW cylinder is to be connected, fit locking cap
with inserted flat gasket to connection RS.
For additional installation steps:
heating circuit quick installation system.
Fig. 22
Condensate drain without neutralising system
1
Acid-resistant condensate hose
2
Hose clip
3
Siphon
2
3
1
USER INFORMATION
B
Ensure that the siphon is always filled
with water and never runs dry. This pre-
vents unpleasant odours.
B
Ensure that the condensate drain is fit-
ted correctly.
SYSTEM DAMAGE
from leaking connections.
B
Connect pipes without stress to the boi-
ler connections (
Fig. 23
Fitting the return connector
1
Flat gasket
2
Tee
3
Locking cap
RK/RS: Return connection G 1¼
RK: Boiler return G 1¼
RS: DHW cylinder return G 1
3
1
2
1
RS
RK/RS
RK