Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed.
Press "Display" to call up a submenu. "PERIM HTG"
or "FLOOR HTG" appears.
Turn the dial until "OASETBACK" is displayed.
+
Hold down the "Display" key and turn the dial until the required value appears
(in this case "OASETBACK").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
OASETBACK
RMSETBACK
Input range
Factory setting
Type of setback
Outdoor setback
Room setback
Setback
Boiler off
Outdoor setback
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
4
1
8
Heating circuit data