7.7
Maximum boiler temperature
The maximum boiler temperature is the highest target temperature the boiler will
reach. The burner should switch off no later than when this temperature is
reached (this applies to heating mode and DHW mode).
The factory default is 176°F (80°C).
Changing the maximum OFF temperature
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "BLR TEMP" is shown.
Press "Display" to call up a submenu.
"FREEZE TEMP" appears.
Turn the dial until "MAXTEMP 1" is shown.
+
Hold down "Display" and turn the dial until the
required value appears (in this case 167°F
(75°C)).
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
176
MAXTEMP 1
°F
167
MAXTEMP 1
°F
USER NOTE
Ensure that the boiler water aquastat dial is set above the maximum boiler
temperature, as it will overwrite the maximum boiler temperature.
Input range
Factory setting
Maximum OFF temperature
158°F – 210°F
(70°C – 99°C)
176°F (80°C)