7.1
System frost protection
The controls is equipped with a system frost protection function.
If the outdoor temperature drops beneath the frost protection limit, the heating
system pump (contacts 61/63) will be started.
The factory default for the frost protection limit is an outdoor temperature of
41°F (5°C).
The setting applies to all heating circuits.
Changing the system frost protection
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "BLR TEMP" is shown.
Press "Display" to call up a submenu.
"FREEZE TEMP" appears.
+
Hold down the "Display" key and turn the dial until the desired value
appears (in this case "41°F").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
41
FREEZE TEMP
°F
43
FREEZE TEMP
°F
USER NOTE
The value of the "OASETBACK" setback type is also limited to the freeze
protection limit. The setting applies to all heating circuits.
Input range
Factory setting
System frost protection
-4°F – 50°F (-20°C – 10°C)
41°F (5°C)