Changing the differential temperature
+
Press the "Display" key and "Install" key at the same time to call up the service
level. "AMERICAN" appears as the first main menu.
Turn the dial until "CIRCUIT 01" or "CIRCUIT 02" is displayed.
Press "Display" to call up a submenu.
"PERIM HTG" or "FLOOR HTG" appears.
Turn the dial until "ROOM COMP" is shown.
+
Hold down the "Display" key and turn the dial until the desired value appears (in
this case "OFF").
Release "Display" to store your input.
Press "ENTER" to return to the next higher level.
6
ROOM COMP
°F
OFF
ROOM COMP
Input range
Factory setting
Differential temperature
OFF
2 – 18°F (1°C – 10°C)
6°F (3°C)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
3
9
8
Heating circuit data