Boiler inspection and maintenance
Logano GC 144 II – 6 720 808 893 (2017/02)
28
Fig. 42 Troubleshooting the GC 144 II
S
TART
Room thermostat (control) signals heat requirement
Vent damper (if installed) opens.
Ignition spark generator operates
• ignition gas valve opens.
Pilot flame stand by
• ignition spark generator stops.
• main gas solenoid valve opens.
Main burner operation
• pilot assembly monitors ignition flame.
S
pecified thermostat value (control) reached
Main and ignition gas valves close, gas burners ex-
tinguished, vent damper (if installed) closes.
Ignition burner operation
Ignition flame burns, automatic
ignition signals steady ignition
flame.
or
ignition flame does not burn,
pilot assembly starts ignition at-
tempt, switches off after 90
seconds.
END
PHA
S
E 1
Ignition attempt
PHA
S
E 2
Main burner
operating
Power interruption
System switches off. Does
the system restart when
power is restored?
Pilot flame fault
Main gas valve closes,
ignition module starts
ignition attempt.
6 720 804 440-5