3
Liquid Propane conversion
Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!
6
Fig. 6
Opening the retaining clips
B
Remove the burner cover together with the fan unit and
the gas valve (
Æ
fig. 7).
Fig. 7
Removing the burner cover with the gas/air unit
B
Undo the 3 screws (
Æ
fig. 8, [1]) and remove the gas
valve with the venturi from the fan unit (
Æ
fig. 8, [2]).
B
Take the gas valve and venturi from the conversion kit
# 7746900499.
Fig. 8
Removing the screws and gas valve with venturi
B
Install the venturi and gas valve of the conversion kit on
the fan unit using a new O-ring (
Æ
fig. 9) and follow the
instructions above in reverse order.
Fig. 9
Placing a new O-ring on the fan unit
B
Install the gas flange from the natural gas assembly on
the new gas valve (
Æ
fig. 10, [1]).
Fig. 10 Installing the gas flange
Thermal
power
gas
boiler
Type
of gas
supply
Altitude
[ft (m)]
Gas orifice
diameter
[inch
(mm)]
Venturi
article
number
GB162-
80 kW/
100 kW
Natural
gas
0-4,000
(0-1,220)
0.331(8.40)
73983
LPG P
0-4,000
(0-1,220)
4.70(0.193)
73983
Tab. 1
Gas orifice diameter
6720615033-007.1TD
6720615033-008.1TD
1
2
6720615033-009.1TD
6720615033-013.1TD
6720615033-014.1TD
1
2