background image

3

 

Liquid Propane conversion

Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!

10

3.8

Lighting Instructions

For your safety, read before lighting.

This boiler is equipped with an ignition device which 
automatically lights the pilot. Do not try to light the pilot by 
hand.

Check for smell of gas around the boiler area.
Be sure to smell next to the floor because some gas is 
heavier than air and will settle on the floor.

Do not use this boiler if any part has been under water. 
Immediately call a qualified service technician to inspect 
the boiler and to replace any part of the control system 
and any gas control which has been under water.

DANGER: 

What to do if you smell gas:

B

No open fire! Do not smoke!

B

Avoid formation of sparks! Do not touch 
any electric switch, phone, electric plug or 
bell!

B

Shut off main gas supply.

B

Open windows and doors!

B

Notify all occupants!

B

Leave the building!

B

Immediately call your gas supplier, heating 
contractor or fire department from a 
phone outside the building!

WARNING: 

due to not following these instructions.

B

If you do not follow these instructions 
exactly, a fire or explosion may result 
causing property damage, personal injury 
or loss of life.

B

Follow these operating instructions.

Содержание GB162-80 kW

Страница 1: ...requirements of the authority having jurisdiction The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or deat...

Страница 2: ...following symbols 3 2 Parts list for converting the boiler to propane 4 3 Liquid Propane conversion 5 3 1 Shut down the boiler 5 3 2 Changing the gas valve assembly 5 3 3 Testing for gas leaks 7 3 4...

Страница 3: ...ollowing symbols DANGER Indicates the presence of hazards that will cause severe personal injury death or substantial property damage WARNING Indicates the presence of hazards that can cause severe pe...

Страница 4: ...rts list for converting the boiler to propane Conversion kit propane for the GB162 80 kW 100 kW 7746900499 includes assembly 774601703A 1 gas valve propane venturi orifice 774600958A these instruction...

Страница 5: ...tion anti clockwise fig 2 Fig 2 Opening the boiler door 3 2 Changing the gas valve assembly B Loosen the screw connection on the gas valve fig 3 1 and pull the plugs fig 3 2 from the gas valve Fig 3 U...

Страница 6: ...rews and gas valve with venturi B Install the venturi and gas valve of the conversion kit on the fan unit using a new O ring fig 9 and follow the instructions above in reverse order Fig 9 Placing a ne...

Страница 7: ...onduit sections up to and including the direct sealing point on the gas burner fitting The maximum test pressure allowed on the input of the gas burner fitting is 60 inch W C 150 mbar B Check the inpu...

Страница 8: ...in 3 5 Checking and adjusting the gas air ratio B Switch off the boiler using the main switch B Loosen the screw plug on the measuring nipple for the burner pressure by 2 rotations fig 15 1 B Set the...

Страница 9: ...Carrying out a tightness test in operating conditions B Check all gaskets and joints in the burner gas circuit for leaks while the burner is operational using a leak detection agent 3 7 Measuring the...

Страница 10: ...ly call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water DANGER What to do if you smell gas B No open f...

Страница 11: ...as Then smell for gas including near the floor If you smell gas STOP and see the safety information on page 10 If you do not smell gas go to the next step B Install the casing again B Open the gas shu...

Страница 12: ...6720615033 0004...

Отзывы: